Table 26. SAN c-type Director Power Supplies (continued)
Description
Output capacity
Component Power Requirements and Heat Dissipation
When sizing the air-conditioning requirements for an installation, consider heat dissipation. The power
and heat associated with an IBM SAN c-type Directors varies based upon the following considerations:
• Power supply type
• Switching module type and number of switching modules installed
• Average switching traffic levels
Table 27 on page 140 lists the power requirements for the components of the SAN c-type Director.
Note : Unless noted otherwise, the power requirement data listed under the Maximum Power Required
column in Table 27 on page 140 is based on the worst-case conditions that are unlikely in a data center
environment.
Table 27. Requirements for 3000 W AC Power Supplies
Module Type/ Product
Number
SAN c-type Director 48
port 32Gbps Switching
Module
24/10 port SAN Extension
Module
SAN c-type Supervisor-4
Module
SAN c-type Director
Supervisor-1E Module
SAN c-type Director
Supervisor-1 Module
SAN768C-6 Crossbar
Switching Fabric1 Module
SAN384C-6 Crossbar
Switching Fabric1 Module
SAN192C-6 Crossbar
Switching Fabric1 Module
SAN384C-6 Crossbar
Switching Fabric3 Module
SAN192C-6 Crossbar
Switching Fabric3 Module
140 IBM Storage Networking SAN192C-6, SAN384C-6 and SAN768C-6: SAN192C-6, SAN384C-6 and
SAN768C-6 Installation, Service, and User Guide
Quantity
4 (SAN192C-6)
8 (SAN384C-6)
16 (SAN768C-6)
2
6
Specification
1500 W maximum (100 to 120 VAC) 3100 W
maximum (200 to 210 VAC)
3500 W maximum (215 to 240 and 277 VAC)
3100 W maximum (200 to 215 VDC)
3500 W maximum (220 to 380 VDC)
Power Required (watts)
Maximum
350
480
120
265
190
300
150
85
150
85
Typical
260
450
110
160
110
160
135
64
135
64