3.3 Technical Specifications

Table 3 PRO3200 Technical Specifications

Category
Primary Power
Memory and
Clock Backup
Ports
Inputs
Cable requirements
Environmental
Mechanical
Specifications subject to change without notice.
Caution:
18AWG wires.
POLARITY for 12 VDC power is important. Make sure the +12 VDC is connected to the
Note:
terminal labeled +12V and the return is connected to the terminal labeled GND.
PRO3200 (PRO32IC) Installation and Configuration Guide, Document 800-15494
Description
WARNING: PRO3200 is manufactured for use in
low-voltage, Class 2 circuits only.
12Vdc nominal with an operating range of 10 to 14Vdc., 300mA
maximum.
12Vdc @ 240mA (325mA with CoBox-Micro) nominal.
3Volts Lithium, type BR2325, BR2330, CR2330.
Port 0
Port 1
Port 2 & 3
2 non-supervised, dedicated for cabinet tamper and power fault
monitoring.
Power:
RS-485:
RS-232:
Ethernet:
Alarm input:
Temperature:
Humidity:
Dimensions:
Weight:
Locate the power source as close to this board as possible. Connect power with minimum of
10Base-T/100Base-TX Ethernet.
RS-232 or 2-wire RS-485: 9,600 to 115,200
bps, async.
2-wire RS-485: 2,400 to 38,400 bps, async.
1 twisted pair, 18 AWG.
24AWG, 4,000ft (1,200m) maximum, twisted
pair with shield. 120 ohm.
24AWG, 25ft (7.6m) maximum.
Cat 5.
1 twisted pair, 30 ohms maximum.
0 to 49°C, operating
-55 to +85°C, storage
0 to 85% RHNC
5.5 in. (137.7mm) W x 9 in. (228.6.4mm) L
x .75 in. (19.05mm) H
7.1 oz. (201 gm) nominal
PRO3200 Installation
Setting Up the PRO3200 Hardware
13