Technical Specifications - Honeywell CD3000M-3PH User Manual

Thyristor unit up to 90a
Table of Contents

Advertisement

Honeywell

2. Technical specifications

2.1 General Features:
Operating temperature
Voltage power supply
Input signal
Firing mode
Auxiliary voltage supply
Fan voltage supply
Heather break alarm
Line Drop Voltage
Mounting
Protection
2.2 Input features
Input signal
SSR
Analog 0÷10V
Analog 4÷20mA
Potentiometer
10K ohm
www.honeywell.com/imc
CD3000M-3PH up to 90A
0÷40°C for higher temperature see derating curve
24V minimum, 480V max and 600V on request
SSR
4÷20 mA
0÷10V
potentiometer (10k ohm)
customer configurable with automatic zero/span calibration
One of these firing modes can be configured on line via serial port
Zero Crossing (ZC)
Burst Firing (BF)
230V range (230 ±15%) 10VA
460V range (380 –15%) ÷ (460 +15%); 10VA
(sincronized with supply Voltage)
230V range (230 ±15%) 10VA
460V range (380 –15%) ÷ (460 +15%); 10VA
(sincronized with supply Voltage)
Discrimination better than 20%. Circuit microprocessor based to
diagnose partial or total load failure and short circuit on Thyristors.
Latching alarm plus reset. Relay output 0,5A at 125V
Automatic compensation ±15% of supply voltage with analog input
Bulk head mounting
IP20
Maximum
current drain
5mA constant current
-
-
Input
ON condition
Impedance
≥4V - max 30V
8200 ohm
100 ohm
8200 ohm
6
User's Manual
OFF condition
≤1V

Advertisement

Table of Contents
loading

Table of Contents