Water Shortage:
•
o Min Water/Hour: TRIO will send an alarm if the water flow is less than this amount.
Range: 0 – 999 gallons/liters.
o Enable Water Shortage Alarm: Define the period in which the alarm is active, 24 hours a
day or specific time frames.
Potentiometer: Enable Potentiometer Alarm: TRIO will send an alarm if potentiometer-controlled
•
inlets are not opening to the required levels. Define the period in which the alarm is active, 24
hours a day or specific time frames.
21.2 Viewing the Alarms
On the Main Menu bar, click
•
Click
•
21.3 Defining the Auxiliary Alarms
The auxiliary alarm provides an additional method for adding alarm functions to specific relays. This
function compares the relay's current state to its defined state (normally open, normally close). If the relay
is not in its defined state, TRIO sends an alarm. You can define the auxiliary alarms to operate during
specific time periods. Use this alarm for those relays controlling important functions.
Define at least one sensor as an auxiliary input in Mapping Devices, page 50.
1. Go to Control > Auxiliary Alarm
.
to acknowledge all alarms or acknowledge each one as required.