SPECIFICATIONS

Table 1 Line Mode Specifications
MODEL
Input Voltage Waveform
Nominal Input Voltage
Low Loss Voltage
Low Loss Return Voltage
High Loss Voltage
High Loss Return Voltage
Max AC Input Voltage
Nominal Input Frequency
Low Loss Frequency
Low Loss Return Frequency
High Loss Frequency
High Loss Return Frequency
Output Short Circuit Protection
Efficiency (Line Mode)
Transfer Time
Output power derating:
When AC input voltage drops to 170V,
the output power will be derated.
PIP3624MT
Sinusoidal (utility or generator)
230Vac
170Vac± 7V (UPS);
90Vac± 7V (Appliances)
180Vac± 7V (UPS);
100Vac± 7V (Appliances)
280Vac± 7V
270Vac± 7V
300Vac
50Hz / 60Hz (Auto detection)
40± 1Hz
42± 1Hz
65± 1Hz
63± 1Hz
Circuit Breaker
>95% ( Rated R load, battery full charged )
10ms typical (UPS);
20ms typical (Appliances)
28
PIP5648MT

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pip5648mt