Table 1 Line Mode Specifications
INVERTER MODEL
Input Voltage Waveform
Nominal Input Voltage
Low Loss Voltage
Low Loss Return Voltage
High Loss Voltage
High Loss Return Voltage
Max AC Input Voltage
Nominal Input Frequency
Low Loss Frequency
Low Loss Return Frequency
High Loss Frequency
High Loss Return Frequency
Power Factor
Output Short Circuit Protection
Efficiency (Line Mode)
Transfer Time
PIP5048MKX
Sinusoidal
230Vac
110Vac± 7V
120Vac± 7V
280Vac± 7V
270Vac± 7V
300Vac
50Hz / 60Hz (Auto detection)
46(56)± 1Hz
46.5(57)± 1Hz
54(64)± 1Hz
53(63)± 1Hz
>0.98
Line mode: Circuit Breaker
Battery mode: Electronic Circuits
93% (Peak Efficiency)
Line modeBattery mode 0ms
InverterBypass 4ms
35