4010 Quick CFIG

Overview

The Quick CFIG option can be used instead of manual programming. Quick CFIG automatically
detects new hardware, and assigns default settings which you can modify later by using the
programmer manually.

Quick CFIG Steps

To add one or more 4009 TrueAlert Addressable Controllers using Quick CFIG:
1. Press the MENU button, and then press NEXT until the display reads Menu: [Quick CFIG].
2. The display reads Please Wait... Fire Alarm Operation Suspended. After
3. The Quick CFIG: [Reconfigure All Hardware] menu item appears.
4. Press ENTER at the prompt warning you that this will delete or change the existing
5. Press ENTER once again to begin automatically detecting new hardware. The display
6. The display notifies you that the configuration has changed, and prompts you to either
7. From the Programming: [Configure Points] menu item, press NEXT until
Press ENTER.
Note: The Quick CFIG menu item does not appear unless you have entered a valid
password with the appropriate access level. See "Step 1: Starting the
Programmer," in this chapter.
a moment, it reads Press <ENTER> for Programming. Press <EXIT> to
resume operation. Press ENTER.
If you are configuring a new job, press ENTER.
If you are configuring an existing job, press NEXT so that
Quick CFIG: [Auto Detect NEW Hardware] comes up, and press ENTER.
configuration.
reads ** Detecting new Hardware **, and soon changes to
** Scanning for IDNet Devices **. After a few minutes, the display reads
Automatic Hardware Detection Completed, along with the number of
IDNet devices that were added. Finally, you are prompted to either press ENTER to go
back to the Quick CFIG menu, or EXIT.
To go back to the Quick CFIG menu, press ENTER and skip the rest of the
instructions below.
To stop programming and save your changes, press EXIT and continue to step 6.
restore, save, or continue. Use the arrow buttons, and press ENTER on your selection.
To save your latest changes, select Save and skip the rest of these instructions.
To cancel your latest changes and restore the 4010 back to the previous
configuration, select Restore and skip the rest of these instructions.
To go back to the previous screen, which allows you to enter the manual programming
menu, select Continue and refer to the "4010 Programming Steps" section.
the Configure Point: [NACs] menu item comes up. At this point, refer to
"Step 3: Configuring 4009 SLC Point Types" to set the correct point types. When you
finish "Step 3," you will be done with the configuration. You can continue on to
"Step 4: Editing Point Labels," or to "Step 5: Saving a Configuration."