4010 Programming Steps,
Step 5:
1. Press NEXT until you get to Programming: [Save CFIG], and press ENTER. Press
Saving a
Configuration
2. The display indicates the panel is saving and then restoring the CFIG and the labels.
Step 6:
To set audible signal types for audible notification appliances,
Specifying Signal
Operation
1. Log in and open the Programming menu.
2. Press NEXT until the Programming: System Options menu item appears. Press
3. Press NEXT until System Options: TrueAlert Non Adr. Horn appears,
4. Use the NEXT and PREVIOUS buttons to scroll through the list of options for TrueAlert
Continued
ENTER again at the prompt.
When the system is done saving, it reboots. Your passcode is cleared from the system,
and you have to log in again if you want to continue programming (i.e., to add, edit, or
delete points).
ENTER.
and press ENTER.
Non-Addressable NACs (in this case, TrueAlert SLCs) that appear in the New: field.
The choices are Temporal, Steady, and Slow March. When you make your
selection, press ENTER. Press ENTER a second time to confirm your choice.