Installing Option Interfaces

Overview

The 4009 TrueAlert Addressable Controller supports several option add-on cards:
4009-9812 Class A Adapter Option Card. Allows fault tolerance in the case of open circuit
wiring faults. One card provides Class A/Style 6 functionality for three TrueAlert SLCs. See
4009-9812 Class A Adapter Option Card Installation Instructions (574-763).
4009-9809 IDNet Repeater Option Card. Regenerates and provides a power and distance
boost for the IDNet channel. Takes the IDNet signal from the 4009 receiver and retransmits it on
its output side at host panel IDNet levels. See IDNet Repeater Option Card Installation
Instructions (574-327).
4009-9810/-9811 Fiber Optic Receiver Option Card. Works with the IDNet Fiber
Transmitter to form a fiber optic link from an IDNet channel to a remote TrueAlert Addressable
Controller. The fiber optic link allows remote buildings (within 3,000 ft (914.4 m)) to connect to
the IDNet channel, and to minimize susceptibility to electrical transients. See Fiber Optic Link
Option Installation Instructions (574-182).
Connectors are provided on the base assembly of the 4009 system board to support the available
option cards. Optional hardware must be configured with the Hardware Configuration DIP
Switch (SW4), described in Table 2-1 on page 2-4, for proper system operation.