Step 3: Configuring 4009 Slc Point Types; Step 4: Editing Point Labels - Simplex TrueAlert 4009-9401 Installation Manual

Addressable
Hide thumbs Also See for TrueAlert 4009-9401:
Table of Contents

Advertisement

4010 Programming Steps,
Step 3:
1. Press NEXT until the Configure Point: [NACs] menu item appears. Press ENTER.
Configuring 4009
2. The display reads NAC Circuit: SIG 1 with a point type of Signal Circuit.
SLC Point Types
3. The Function: [Edit Device Type] menu item appears. Press NEXT so that
4. The display now reads [SSIGNAL: Fire Signal (On Til Silence)]. This is
5. When prompted, press ENTER to confirm your selection. The display reads
6. At this point, repeat steps 1 through 5 for each 4009 TrueAlert Addressable Controller
Step 4:
1. From the Configure Point: [NACs] menu item, scroll up to the
Editing Point Labels
2. The Function: [Edit Device Type] menu item comes up. Press NEXT until
3. The part of the display that says IDNet M1-x: 4009A NAC 1 is now editable. Use
4. Repeat steps 1 through 3 for every 4009 TrueAlert SLC.
5. Change IDNet M1-x: 4009A NAC 1 to say "4009T COMMON CLASS A
6. Press EXIT to return to Programming: [Configure Points].
Continued
Press NEXT or PREVIOUS until IDNET M1-x: 4009A NAC 1 with a point type of
Signal Circuit appears. Press ENTER.
Function: [Edit Point Type] comes up. Press ENTER.
only one of the available point types. Press PREVIOUS to display other point types.
Press ENTER on one of the two point types that apply to 4009 SLCs:
[QALERT: TrueAlert Non Adr. (Gen)]. Makes the SLC respond to
Custom Control commands.
[SQALERT: TrueAlert N.A. Horn(On Til Sil)]. Makes the SLC
respond to normal system control.
** Operation Complete **, and you are returned to the
Configure Point: [NACs] display.
you need to add.
4009 NAC points you just modified. Each one displays an M1-x address and reads
TrueAlert N.A.NAC under it. Press ENTER on the first SLC point you want to edit.
the display reads Function: [Edit Point Label], and then press ENTER.
the PREVIOUS and NEXT buttons to select alphanumeric characters. When you have
selected the correct character, use the right and left arrow buttons to move to other
characters. When you are done, press ENTER and then press ENTER again to confirm
your selection. The display will then read **Operation Complete**.
TROUBLE".
Note: An alternate way to edit labels is to clear the point label completely and then
add text. To do this, press ENTER on the Configure Point: [NACs]
menu item, use the NEXT or PREVIOUS buttons to scroll to the
Function: [Clear Point Label] item, press ENTER, select an
IDNet M1-x entry, and press ENTER again. This deletes all the characters
on the top line of the display and lets you enter and save text as described in
step 3.