System Trouble Messages - Simplex TrueAlert 4009-9401 Installation Manual

Addressable
Hide thumbs Also See for TrueAlert 4009-9401:
Table of Contents

Advertisement

Hardware Components,
System Trouble
Tables 1-1 and 1-2, below, list the messages that appear on the FACP displays for each type of
Messages
trouble.
Note: On hardwired systems, all troubles are displayed as "Open Circuit Trouble."
Trouble Description
AC Fail
Low/Missing Battery
Running on Depleted Battery
Memory/Checksum Error
RUI Comm Fail
Hardware
Configuration Mismatch
Channel Controller Trouble
Negative Earth*
Positive Earth*
Hardware Configuration Error
Memory Test Error
Charger Trouble
Trouble Description
Channel Fail
Short Circuit
Duplicate Appliance
Missing Appliance
Extra Appliance
Class A Trouble
Earth Trouble*
Isolator Trouble
Bad Download
Address Out of Range
*Refer to "Isolating Earth Grounds" on the next page.
Occurs for all circuits not assigned to the TrueAlert point type of QALERT or SQALERT.
Continued
Table 1-1. System Trouble Messages
4010 IDNet Display
AC Power Fail
Battery Fault
Battery Fault
4009A No Answer
--
TrueAlert Non-Addressable NAC Open
4009A No Answer
Negative Earth Ground
Positive Earth Ground
4009A No Answer
4009A No Answer
Battery Fault
Table 1-2. Channel Trouble Messages
4010 IDNet Display
TrueAlert Non-Addressable NAC Open
TrueAlert Non-Addressable NAC Short
TrueAlert Non-Addressable NAC Open
TrueAlert Non-Addressable NAC Open
TrueAlert Non-Addressable NAC Open
Custom Label
TrueAlert Non-Addressable NAC Open
TrueAlert Non-Addressable NAC Open
TrueAlert Non-Addressable NAC Open
TrueAlert Non-Addressable NAC Open
1-9
firealarmresources.com
4100/4020 RUI Display
AC Voltage Status
Battery Low/Disconnected
Running on Depleted Battery
Card Missing/Failed
Card Missing/Failed
Hardware Configuration
Channel Comm. Failure
Negative Earth Ground
Positive Earth Ground
Card Missing/Failed
Card Missing/Failed
Battery Charger
4100/4020 RUI Display
Card x Channel Fail
Card x Short Circuit
Address, Channel Duplicate
No Answer
Extra Device
Common Class A Trouble
Negative Earth Ground or Positive
Earth Ground
Isolator Short
--
Extra Device
Continued on next page