System Configuration

Overview

This section describes how to use the DIP switches on the 4009 TrueAlert Addressable Controller
board for setting addresses and optional features.
SLC Appliance DIP
The SLC Appliance Switches (SW1, SW2, SW3) are 8-position DIP switches. Use these switches
Switches
to set the number of appliances connected to each SLC. SW1 corresponds to SLC 1, SW2
(SW1, SW2, SW3)
corresponds to SLC 2, and SW3 corresponds to SLC 3. A maximum of 63 appliances or 2.5 amps
of power may be specified per SLC channel (refer to Field Wiring Diagram 842-158). Refer to
Figure 1-2 to locate the switches on the system board. Refer to Figure 2-2, below, to specify the
correct number of appliances for each SLC channel.
Use a small screwdriver or pen to set the switches.
Notes:
DIP switch in "1" position is ON while DIP switch in "0" position is OFF.
SW1, SW2, and SW3 are disabled when the RUI host interface is selected.
LSB
1
ON
OFF
RESERVED FOR
FUTURE USE
DIP
SWITCHES
1 THRU 4

Figure 2-3. SLC Appliance Settings (SW1, SW2, SW3)

firealarmresources.com
DIP SWITCH IS SHOWN
DIPSWITCH IS SHOWN
MSB
SET AT ADDRESS 7.
2
3
4
5
6
7
8
NOT USED
DIP SWITCHES 5 AND 6
0000
1000
0100
1100
0000
0
16
32
48
1000
1
17
33
49
0100
2
18
34
50
3
19
35
51
1100
0010
4
20
36
52
1010
5
21
37
53
6
22
38
54
0110
1110
7
23
39
55
0001
8
24
40
56
1001
9
25
41
57
10
26
42
58
0101
1101
11
27
43
59
0011
12
28
44
60
1011
13
29
45
61
14
30
46
62
0111
1111
15
31
47
63
2-4
SET AT ADDRESS 7.
1 = ON
0 = OFF
Continued on next page