Simplex TrueAlert 4009-9401 Installation Manual page 24

Addressable
Hide thumbs Also See for TrueAlert 4009-9401:
Table of Contents

Advertisement

System Configuration,
Hardware
Manual Real Appliance Test. Activates a test mode so that appliances can be manually tested
Configuration DIP
one at a time. The manual real appliance test makes a given notification appliance report its
Switch (SW4),
address and emits an alarm. Place a magnet on the appropriate area of the notification appliance to
continued
initiate a real appliance test. The LED emits one long flash denoting the test acknowledge signal,
and then another long flash denoting the first digit (always zero) of the appliance address. The
LED then flashes one to six times to denote the second digit of the address, pauses, and flashes
one to nine times to indicate the third digit of the address. A zero is always indicated by one long
flash. After the LED flashes, the appliance goes into alarm for 2 to 3 seconds.
Manual Silent Appliance Test. Like the real appliance test mode, this allows appliances to be
manually tested, one at a time. The manual silent appliance test makes a given notification
appliance report its address without emitting an alarm. Place a magnet on the appropriate area of
the appliance to initiate a silent appliance test. The LED emits one long flash denoting the test
acknowledge signal, and then another long flash denoting the first digit (always zero) of the
appliance address. The LED then flashes one to six times to denote the second digit of the address,
pauses, and flashes one to nine times to indicate the third digit of the address. A zero is always
indicated by one long flash. When the address is done, the LED illuminates once more for 2 to 3
seconds.
Class A Adapter Card Options. Refer to Table 2-2, below, for a description of what happens
when switch 2 is set.
Note: In Table 2-2, "Yes" denotes the Class A Option Card has been correctly wired and
*In Hardwired mode, this condition clears once a Class A Card is correctly installed and the Addressable
Controller is reinitialized. In the 4010 and 4100, the message clears only after the Class A Card is correctly
installed and the SYSTEM RESET button is pressed at the host panel.
RUI Host. Selected when the TrueAlert Addressable Controller is used with a 4100 or 4020
FACP. The Addressable Controller LEDs will display a Comm Trouble if the RUI channel is not
connected.
IMPORTANT: The Addressable Controller cannot be connected to hardwired NAC
Continued
installed in the Addressable Controller.
Class A Card Connected
(SW4) Switch 2
to Addressable
Setting
ON
OFF
channels (TB7) and a RUI host (TB1) at the same time.
firealarmresources.com
Table 2-2. (SW4) Switch 2
Controller?
Yes
No
Yes
Configuration Mismatch Trouble
No
2-6
System Status
Normal
Class A Trouble*
Normal
Continued on next page