- 2 - INSTALLATION
2.1 MOUNTING DIGIDRIVER
The management and power unit DIGIDRIVER should be placed on a non-flammable flat surface in any
orientation or fixed by four screws in a 19" rack. There are four mounting holes on the housing as shown
in figure 7.
2.2 MAXIMUM CABLE DISTANCE
Max cable distance between DIGIDRIVER - first fixture connected:
• DIGIDRIVER - DIGIBAR160 = 20 m
• DIGIDRIVER - DIGITILE144 = 30 m
• DIGIDRIVER - DIGISTRIP40 = 10 m
• DIGIDRIVER - DIGITUBE = 20 m
Max cable distance between two fixtures:
• 2 DIGIBAR160 = 1 m
• 2 DIGITILE144 = 1 m
• 2 DIGISTRIP40 = 1 m
Max distance between DIGIDRIVER - last fixture connected:
• DIGIDRIVER - DIGIBAR160 = 25 m
• DIGIDRIVER - DIGITILE144 = 35 m
• DIGIDRIVER - DIGISTRIP40 = 33 m
DIGI series
Fig.7