Unit 2 Stage Position (POS 6)

These stage positions will only appear if unit 2 is activated by setting
DIPSW2 to ON (see DIP Switches and Slide Switches Table page 36) and
the corresponding stages are used as ventilation stages or as a mist stage
with a 100% duty cycle.
Stage 3 Position 3-POS
This parameter is used to establish the position the inlet will take when
stage 3 of unit 2 is activated. This parameter is adjusted in 1% increments
from 0% to 100%.
Stage 4 Position 4-POS
This parameter is used to establish the position the inlet will take when
stage 4 of unit 2 is activated. This parameter is adjusted in 1% increments
from 0% to 100%.
Stage 5 Position 5-POS
This parameter is used to establish the position the inlet will take when
stage 5 of unit 2 is activated. This parameter is adjusted in 1% increments
from 0% to 100%.
Stage 6 Position 6-POS
This parameter is used to establish the position the inlet will take when
stage 6 of unit 2 is activated. This parameter is adjusted in 1% increments
from 0% to 100%.
Stage 7 Position 7-POS
This parameter is used to establish the position the inlet will take when
stage 7 of unit 2 is activated. This parameter is adjusted in 1% increments
from 0% to 100%.
Stage 8 Position 8-POS
This parameter is used to establish the position the inlet will take when
stage 8 of unit 2 is activated. This parameter is adjusted in 1% increments
from 0% to 100%.

Outside Temperature (POS 7)

Outside Temperature
This parameter displays the outside temperature. This parameter will
appear only if at least one of the units uses an outside probe. If two units
are used and both of them have an outside probe, this temperature will be
the average of the two probes. This reading may modify the inlet position
when no stages are activated or when the inlet is positioning for variable 1
of unit 1. This parameter is displayed to the nearest 0.1° from -58.0°F to
140.0°F (-50.0°C to 60.0°C).
DIP-1C
www.monitrol.com
DIP-1C USER'S GUIDE
Section C-27