USER'S MANUAL
www.monitrol.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the CPS-3M and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Varifan CPS-3M

  • Page 1 CPS-3M USER’S MANUAL www.monitrol.com...
  • Page 2 CPS-3M Although the manufacturer has made every effort to ensure the accuracy of the information contained herein, this document is subject to change without notice due to ongoing product development. WARNING AND PRECAUTIONS Equipment, probe failure, blown fuses and/or tripped breakers may prove harmful to the contents of the building.
  • Page 3: Table Of Contents

    TABLE OF CONTENTS CHAPTER 1 - INTRODUCTION General ................5 Description ...............5 Definition of terms .................6 CHAPTER 2 - INSTALLATION Unpacking ................7 Installation ...............7 Switch Settings ..............8 2.3.1 Line Voltage Selector Switch ...........8 2.3.2 Software Setting DIP Switch ..........8 Connection Procedure .............9 2.4.1 Input Power ..............9 2.4.1.1 115 VAC ................9...
  • Page 4 CPS-3M Zone 1 Record Low Temperature ........24 Zone 1 Record High Temperature .........25 Zone 1 Max Run Time .............26 Zone 1 Main Set PointTemperature ........27 Zone 1 Room Temperature Display ........28 FUNCTION 2 Zone 2 Differential ............29 Zone 2 Delay Timer (actuator 2) ........30 Zone 2 High Temperature Alarm ........31...
  • Page 5: Chapter 1 - Introduction

    Moreover, the CPS-3M is equiped with state of the art logic for extra-accurate ventilation and heating control. The present manual has been published in order to make custom installation and control easier.
  • Page 6: Definition Of Terms

    CPS-3M DEFINITION OF TERMS TEMPERATURE MAIN SET POINT The desired temperature in a room. ROOM TEMPERATURE The actual room temperature AIR INLET/ CURTAIN A device which regulates airflow into a building by controlling the opening or closing of an air passage.
  • Page 7: Unpacking

    Failure to do so may void the warranty! 2.1 UNPACKING Unpack the CPS-3M from its box and inspect contents for damage. Should the contents appear to be damaged, contact your local distributor to return the material .
  • Page 8: Switch Settings

    The CPS-3M is configured for a variety of options via the two following switches: 2.3.1 - Line Voltage Selector Switch This switch is located on the surface of the main (bottom) board and adapts the CPS-3M to 115 VAC or 230 VAC line voltage. 230V 115V See figure 1 2.3.2 - Software setting switch...
  • Page 9: Connection Procedure

    2.4.1 - Input power Use a screwdriver to remove cable knock-outs for the installation of cables on the CPS-3M. Do not power up the CPS-3M until all connections have been completed! 2.4.1.1 - 115 VAC Make sure that the line voltage selector switch is set to 115 VAC.
  • Page 10: Temperature Probe

    These cables can measure up to 500 feet (150 meters). Probes longer than 10 feet (3 meters) must be shielded with a #18AWG aluminum wire, or one bigger. The shield must be connected to the CPS-3M’s SHLD terminal. The connections for 2 temperature probes are illustrated in figure 2, whereas the connections for temperature averaging are illustrated in figure 3.
  • Page 11: Alarm

    Make the normally closed (NC) or normally open (NO) connections as indicated in figure 2. Momentary power interruptions may trigger false alarms! To avoid them, when the CPS-3M is connected to an alarm system, install a time delay relay between the CPS-3M and the alarm system.
  • Page 12 CPS-3M Figure 1 Wiring for 2 actuators and 1 heating unit WARNING!!! SET LINE VOLTAGE TO CORRECT VALUE BEFORE ATTEMPTING TO OPERATE THE CONTROL. Figure 1a Wiring diagram for a three phase motor Page 12 www.monitrol.com...
  • Page 13: Fig 3 Connection Diagram (Average)

    CHAPTER 2 - INSTALLATION Figure 2 Temperature probes Figure 3 Probe connection for temperature averaging in 1 zone Page 13 www.monitrol.com...
  • Page 14 CPS-3M Figure 4 Main (bottom) board: terminal blocks, switch and jumpers. Figure 5 Four wire motor with parallel windings Page 14 www.monitrol.com...
  • Page 15: Chapter 3 - User's Guide

    Control Dials The center dial is the selector dial and is used to select one of the CPS-3M’s 12 primary or 8 secondary functions. The dial to the right of the selector dial is the adjustor dial and is used to adjust the setting of each function or to enter secondary mode.
  • Page 16 (12) to any other secondary function. When secondary functions (2) through (11) are selected, the status window displays a blinking value along with a scrolling LED display. Selection of function (12) switches the CPS-3M back to primary mode. Page 16 www.monitrol.com...
  • Page 17: Zone 2 Room Temperature Display

    If temperature is lower than 42.0°F, Lo is displayed. If temperature is higher than 111°F, Hi is displayed. Viewing the room temperature: • rotate the selector dial to position (1) The room temperature for zone 2 is displayed on the CPS-3M. Page 17 www.monitrol.com...
  • Page 18: Zone 2 Main Set Point Temperature

    CPS-3M ZONE 2 MAIN SET POINT TEMPERATURE (MANUAL MODE) main point establishes target temperature in the building. The main set point temperature is adjusted in 0.5 degree increments from a minimum setting of 42.0°F (5.5°C) to a maximum setting of 111°F (44.0°C).
  • Page 19: Zone 2 Maximum Run Time

    • rotate the selector dial to position (3), • rotate the adjustor dial counterclockwise to decrease the setting, and clockwise to increase The CPS-3M automatically calculates a run time according to temperature variations and the difference between room temperature and the main set point.
  • Page 20: Zone 2 Record High Temperature

    Viewing the highest temperature recorded in zone 2: • rotate the selector dial to position (4) Clearing the high temperature value: • quickly rotate adjustor dial counterclockwise, then clockwise. CLr will be briefly displayed on the CPS-3M Page 20 www.monitrol.com...
  • Page 21: Zone 2 Record Low Temperature

    Lo is displayed. Viewing the lowest temperature recorded: • rotate the selector dial to position (5) Clearing the low temperature value: • Quickly rotate adjustor dial counterclockwise, then clockwise. CLr will be briefly displayed on the CPS-3M. Page 21 www.monitrol.com...
  • Page 22: Heating Set Point

    CPS-3M HEATING SET POINT The CPS-3M has an absolute heating set point; meaning that this function establishes the temperature at which heating goes ON. It stops, then starts again when temperature reaches the heating differential set by position (7). When 2 zones are selected, the temperature considered is the average temperature of the 2 zones.
  • Page 23: Heating Differential

    Adjusting the heating differential: • rotate the selector dial to position (7), • rotate the adjustor dial counterclockwise to decrease the differential, and clockwise to increase it. The differential is displayed on the CPS-3M. Page 23 www.monitrol.com...
  • Page 24: Palier 1 Affichage De La Température (Basse)

    Viewing the lowest temperature recorded in zone 1: • rotate the selector dial to position (8) Clearing the low temperature value: • quickly rotate adjustor dial counterclockwise, then clockwise. CLr will be briefly displayed on the CPS-3M. Page 24 www.monitrol.com...
  • Page 25: Palier 1 Affichage De La Température (Haute)

    Viewing the highest temperature recorded in zone 1: • rotate the selector dial to position (9) Clearing the high temperature value: • quickly rotate adjustor dial counterclockwise, then clockwise. CLr will be briefly displayed on the CPS-3M. Page 25 www.monitrol.com...
  • Page 26: Zone 1 Max Run Time

    • rotate the adjustor dial counterclockwise to decrease the setting, and clockwise to increase The timer’s setting is displayed on the CPS The CPS-3M automatically calculates a run time according to temperature variations and the difference between room temperature and the main set point.
  • Page 27: Zone 1 Main Set Pointtemperature

    • rotate the adjustor dial counterclockwise to decrease the setting, and clockwise to increase The main set point temperature is displayed on the CPS-3M. Manual mode: The actuator motor may be manually controlled by adjusting the main set point to OPN or CLO, thereby causing the air inlet to either remain fully open or closed.
  • Page 28: Zone 1 Room Temperature Display

    C). If temperature is lower than 42.0°F, Lo is displayed. If temperature is higher than 111°F, Hi is displayed. Viewing the room temperature: • rotate the selector dial to position (12) The room temperature for zone 1 is displayed on the CPS-3M. Page 28 www.monitrol.com...
  • Page 29: Zone 2 Differential

    This feature, which greatly reduces equipment wear, represents the inactivity zone for the CPS-3M, that is if the main set point is DIFF reached. The differential is adjusted in 0.5 degree increments from a minimum setting of 0.0°F...
  • Page 30: Zone 2 Delay Timer (Actuator 2)

    • rotate the adjustor dial counterclockwise to decrease the delay, and clockwise to increase it. The delay timer is displayed on the CPS-3M. Example: The delay timer is set to 1 minute. The actuator motor, when called upon to open the air inlet, will operate after a delay of 1 minute.
  • Page 31: Zone 2 High Temperature Alarm

    • rotate the selector dial to position (4), • rotate the adjustor dial counterclockwise to decrease the setting, and clockwise to increase The high temperature relative alarm setting is displayed on the CPS-3M. Page 31 www.monitrol.com...
  • Page 32: Zone 2 Low Temperature Alarm

    • rotate the selector dial to position (5), • rotate the adjustor dial counterclockwise to decrease the setting, and clockwise to increase The low temperature relative alarm setting for zone 2 is displayed on the CPS-3M. Page 32 www.monitrol.com...
  • Page 33: Zone 1 Low Temperature Alarm

    • rotate the selector dial to position (8), • rotate the adjustor dial counterclockwise to decrease the setting, and clockwise to increase The low temperature relative alarm setting for zone 1 is displayed on the CPS-3M. Page 33 www.monitrol.com...
  • Page 34: Zone 1 High Temperature Alarm

    • rotate the selector dial to position (9), • rotate the adjustor dial counterclockwise to decrease the setting, and clockwise to increase it. The high temperature relative alarm setting is displayed on the CPS-3M. Page 34 www.monitrol.com...
  • Page 35: Zone 1 Delay Timer (Actuator 1)

    • rotate the adjustor dial counterclockwise to decrease the delay, and clockwise to increase it. The delay timer is displayed on the CPS-3M. Example: The delay timer is set to 1 minute. The actuator motor, when called upon to open the air inlet, will operate after a delay of 1 minute.
  • Page 36: Zone 1 Differential

    This feature, which greatly reduces equipment wear, represents the inactivity zone for the CPS-3M, that is if the main set point is DIFF reached. The differential is adjusted in 0.5 degree increments from a minimum setting of 0.0°F...
  • Page 37 Page 37 www.monitrol.com...
  • Page 38 CPS-3M Page 38 www.monitrol.com...
  • Page 39: Appendix

    APPENDIX APPENDIX Page 39 www.monitrol.com...
  • Page 40: Troubleshooting

    − Display is Make sure the line voltage selector switch blank is properly set. − Make sure the 10 pin flat cable, between the main board and the CPS-3M faceplate, is properly connected. Page 40 www.monitrol.com...
  • Page 41: Specifications

    APPENDIX SPECIFICATIONS DESCRIPTION VALUE − INPUT POWER 100 mA − 115/230 VAC − 50 / 60 Hz ZONE 1 (relay 1 and 2) − 10 Amp max; 115V/230V Not Fused − 1/2 HP @ 115V − 1 HP @ 230V −...
  • Page 42: Record Form

    CPS-3M RECORD FORM FUNCTION 1 Dial Option Default Setting User Temperature set point #2 5.5 to 44°C 42 to 111°F Actuator max. run time 1 sec. to 4 min. Heating set point 5.5 to 45.0°C 41 to 112°F Heating differential 0.0 to 3.0°C...
  • Page 43: Warranty

    WARRANTY Limited Warranty manufacturered equipment supplied components have gone through rigorous inspection to assure optimal quality of product and reliability. Individual controls are factory tested under load, however the possibility of equipment failure and/or malfunction may still exist. For service, contact your local retailer or supplier. The warranty period shall be for two years from manufacturing date.