Page 2
ECS-4+ Although the manufacturer has made every effort to ensure the accuracy of the information contained herein, this document is subject to change without notice due to ongoing product development. WARNINGS AND PRECAUTIONS Equipment, probe failure, blown fuses and/or tripped breakers may prove harmful to the contents of the building.
TABLE OF CONTENTS CHAPTER 1 - INTRODUCTION General ................5 Description ...............5 Definition of terms .................7 CHAPTER 2 - INSTALLATION Unpacking ................9 Mounting ................9 Switch Settings ..............11 2.3.1 Line Voltage Selector Switch ..........11 2.3.2 Software Settings DIP Switch .........11 Connection Procedure ............12 2.4.1 Input Power ..............12 2.4.1.1 115 VAC ................12...
Page 4
ECS-4+ Heater/Fan 3 Relative Set Point ........26 Air Inlet Relative Set Point ..........27 Air Inlet Static Pressure Set Point ........28 Static Pressure Display ...........29 Reduction per Day ............30 Record Low Temperature ..........31 Record High Temperature ..........32 Room Temperature Display ..........33 SECONDARY FUNCTIONS Fan 1 Motor ..............34 Fan 1 Differential .............35...
CHAPTER 1 - INTRODUCTION 1. GENERAL This document provides a description of the ECS 4+ control. This document is organized as follows: • Introduction • Installation • User’s Guide • Appendix 1.1 DESCRIPTION Congratulations on the purchase of your ECS 4+ environmental control system.
Page 6
ECS-4+ The second stage provides control over a second variable speed fan. This second stage is also fully programmable for settings such as minimum speed, relative set point, etc. The third stage controls either a heater for colder climates, or a third single speed fan where additional cooling is required.
CHAPTER 2 - INSTALLATION MAIN SET POINT The desired room temperature. Other temperature settings on the ECS-4+ are relative to the main set point temperature. RELATIVE SET POINT A value added to or subtracted from the main set point which results in a new temperature at which a desired action starts or stops.
CHAPTER 2 - INSTALLATION Chapter 2 describes the installation of the ECS-4+control. The manufacturer recommends that the installation instructions which follow be adhered to as closely as possible, and all work be performed by a certified electrician. Failure to do so may void the warranty! 2.1 UNPACKING...
Page 10
ECS-4+ Use a screwdriver to remove the lower terminal cover exposing two mounting holes located at the bottom left and right corners of the control panel box as shown in figure 1. A third mounting hole is located on the rear side of the control panel box.
CHAPTER 2 - INSTALLATION 2.3 SWITCH SETTINGS The ECS-4+ is configured for a variety of options via two switches: the line voltage selector switch, and the software settings DIP switch. These switches are described in the following two sections. 2.3.1 - Line Voltage Selector Switch This switch is located on the surface of the main (bottom) board and adapts the control panel for 115 VAC or 230 VAC line voltage.
ECS-4+ 2.4 CONNECTION PROCEDURE For the connection procedures which follow refer to Figures 2 through 6. 2.4.1 - Input power To facilitate the installation work, the unit is shipped with two cable knock-outs removed. If two cable paths are not sufficient, remove other cable knock-outs with a...
CHAPTER 2 - INSTALLATION 2.4.5 - Air Inlet Baffle Board Stage 4 provides two dry contact which control a linear actuator motor used to operate an air inlet baffle board. One dry contact closure is used to operate the motor winding which extends the actuator arm outwards, and one dry contact closure is used to operate the motor winding which retracts the actuator arm inwards.
ECS-4+ 2.6 ALARM The ECS 4+ provides a normally open and normally closed dry contact for alarming low or high temperature conditions. In addition, this same contact can be used to signal a power failure. This contact may be connected to an alarm system, or directly to a siren and/or auto-dialer.
Page 15
CHAPTER 2 - INSTALLATION Figure 2 Two fans, one actuator and one heating unit Notes for Figures 2 and 6 Power cut and protection devices in case of overload. Only use fans that have thermal protection devices. Terminals 8, 10, and 11 are internally connected. Connect the ground wire to ground terminal 13.
Page 16
ECS-4+ Figure 3 Probes and Alarm Wiring Figure 4 Temperature Averaging Probe connections Page 16 www.monitrol.com...
Page 17
CHAPTER 2 - INSTALLATION Figure 5 Main Board: Terminal block, switches, fuses and ground. Page 17 www.monitrol.com...
CHAPTER 3 - USER’S GUIDE The ECS 4+ front panel shown above features a LED status window and two control dials which are respectively used to select a function and adjust a setting. LED STATUS WINDOW The LED status window features a 3 digit LED readout for the display of temperature in Fahrenheit or Celsius, pressure level, and programmable settings.
Page 20
ECS-4+ Fan 2 minimum speed Heater/Fan 3 relative set point temperature Either the air inlet relative temperature, or the air inlet static pressure set point Static room pressure display Ramping Record low temperature display Record high temperature display Room temperature display Any one of these functions is selected by rotating the Selector dial to the corresponding number and associated graphical image printed on the faceplate of the panel.
CHAPTER 3 - USER’S GUIDE PRIMARY FUNCTIONS MAIN SET POINT TEMPERATURE The main set point establishes the target temperature in the building. This value is used as the reference point for other temperature settings. The main set point temperature is adjusted in 0.5 degree increments from a minimum setting of 42.0°F (5.5°C) to a maximum setting of 111°F (44.0°C).
ECS-4+ FAN 1 MINIMUM SPEED This function sets the minimum speed of Fan 1 when room temperature is below the main setpoint. This value is entered as a percentage of maximum speed. The Fan 1 minimum speed is adjusted in 2% increments from a minimum setting of 12% to a maximum setting of 100%.
CHAPTER 3 - USER’S GUIDE FAN 1 DUTY CYCLE As long as the actual temperature is below the main set point, Fan 1 operates at the minimum speed, set by Fan 1 minimum speed (primary function 2). The Fan 1 duty cycle sets the percentage of time the fan is ON versus the percentage of time the fan is OFF.
ECS-4+ FAN 2 RELATIVE SET POINT The Fan 2 relative set point establishes the temperature above the main set point at which Fan 2 begins to operate at its minimum speed. The value is a temperature difference from the main set point. The Fan 2 relative set point is adjusted in 0.5 degree increments from a minimum setting of 0.0°F (0.0°C) to a maximum setting of 18.0°F...
CHAPTER 3 - USER’S GUIDE FAN 2 MINIMUM SPEED When the room temperature is at the Fan 2 relative set point, Fan 2 runs at minimum speed set by this function. This value is entered as a percentage of maximum speed. The Fan 2 minimum speed is adjusted in 2% increments from a minimum setting of 12% to a maximum setting of 100%.
ECS-4+ HEATER / FAN 3 RELATIVE SET POINT The Heater/Fan 3 relative set point is the relative set point at which Heater/Fan 3 begins to operate. This value is the temperature difference from the main set point. When a heater is being controlled, the relative set point is below the main set point.
CHAPTER 3 - USER’S GUIDE AIR INLET RELATIVE SET POINT The air inlet relative set point establishes the relative temperature at which the actuator motor begins to open or close the air inlet baffle board. This value is a temperature difference from the main set point.
ECS-4+ AIR INLET PRESSURE SET POINT inlet static pressure point establishes the desired room static pressure level. When the room static pressure rises above the static pressure set point, the air inlet baffle board begins to open. When the static pressure of the room drops below the static pressure set point, the air inlet baffle board begins to close.
CHAPTER 3 - USER’S GUIDE STATIC PRESSURE DISPLAY This function displays the static pressure level of the room. Static pressure is displayed in 0.01” H increments from a minimum display of -20” O , to a maximum display of 20” H O .
ECS-4+ REDUTION PER DAY The reduction per day function automatically reduces the main set point by the set amount every 24 hours. The reduction setting is adjusted in 0.01 degree decrements from a minimum setting of OFF, -0.01°F (-0.01°C) to a maximum setting of -0.99°F (-0.50°C).
CHAPTER 3 - USER’S GUIDE RECORD LOW TEMPERATURE This function displays the lowest recorded temperature since the last clear. The record low temperature is rounded to the nearest 0.5 degree from a minimum display of 42.0°F (5.5°C) to a maximum display of 111°F (44.0°C).
ECS-4+ RECORD HIGH TEMPERATURE This function displays the highest recorded temperature since the last clear. The record high temperature is rounded to the nearest 0.5 degree from a minimum display of 42.0°F (5.5°C) to a maximum display of 111°F (44.0°C). If a temperature higher than 111°F is recorded, Hi is displayed.
CHAPTER 3 - USER’S GUIDE ROOM TEMPERATURE DISPLAY This function displays the room temperature. The Selector dial should normally be left in this position. The room temperature is displayed to the neerest 0.5 degree from a minimum display of 42.0°F (5.5°C) to a maximum display of 111°F (44.0°C) If the temperature is lower than 42.0°F,...
ECS-4+ FAN 1 MOTOR The Fan 1 motor compatibility setting adjusts the control panel outputs to the electrical characteristics of the fan motor. Six choices are available. Using the compatibility table in the Appendix, find the model number of your fan motor and Motor take note of the fan motor compatibility number.
CHAPTER 3 - USER’S GUIDE FAN 1 DIFFERENTIAL The Fan 1 differential setting establishes the temperature at which Fan 1 reaches maximum speed. The value entered is the temperature difference from the main set point. The Fan 1 diferential is adjusted in 0.5 degree increments from a minimum setting of 2.0°F Diff (1.0°C) to a maximum setting of 18°F (10.0°C).
ECS-4+ FAN 2 DIFFERENTIAL The Fan 2 differential setting establishes the temperature at which Fan 2 reaches maximum speed. The value entered is the temperature difference above the Fan 2 relative set point. Diff The Fan 2 diferential is adjusted in 0.5 degree increments from a minimum setting of 2.0°F (1.0°C) to a maximum setting of 18°F (10.0°C).
CHAPTER 3 - USER’S GUIDE FAN 2 MOTOR The Fan 2 motor compatibility setting adjusts the control panel outputs to the electrical characteristics of the fan motor. Six choices are available. Using the compatibility table in the Appendix, Moteur find the model number of your fan motor and take note of the fan motor compatibility number.
ECS-4+ HEATER/FAN 3 HYSTERESIS In order to minimize erratic behavior of Heater/Fan 3 when room temperature is exactly at the relative set point, the hsteresis setting separates this ON/OFF threshhold into two: one ON threshhold and one OFF. This feature greatly reduces equipment wear. Hyst.
CHAPTER 3 - USER’S GUIDE AIR INLET RUN TIMER The air inlet run timer establishes the period of time that the actuator motor operates when opening or closing the air inlet baffle board. The air inlet run timer is adjusted in 1 second increments from a minimum setting of 1 second Run Time to a maximum setting of 60 seconds.
ECS-4+ AIR INLET DELAY TIMER The air inlet delay timer establishes the delay time before the actuator motor begins to operate. The air inlet delay timer is adjusted in 1 minute increments from a minimum setting of 1 Delay minute to a maximum setting of 20 minutes. Adjusting the air inlet delay timer: •...
CHAPTER 3 - USER’S GUIDE MINIMUM RAMPING Minimum ramping is the lowest that the ramping function can adjust the main set point to. This is a safety feature. The minimum ramping setting is adjusted in 0.5 degree increments from a minimum setting of Limit 42.0°F (5.5°C) to a maximum setting of 111°F (44.0°C).
ECS-4+ LOW TEMPERATURE ALARM This function establishes the temperature difference below the main set point that the room can reach before a low temperature alarm is triggered. When a low temperature alarm occurs, an alarm contact is activated and the alarm LED segment lights up on the Alarm panel.
CHAPTER 3 - USER’S GUIDE HIGH TEMPERATURE ALARM This function establishes the temperature difference above the main set point that the room can reach before a high temperature alarm is triggered. When a high temperature alarm occurs, an alarm contact is activated and the alarm LED segment lights up on the Alarm panel.
ECS-4+ MOTOR COMPATIBILITY TABLE CURVE BRAND MODEL VOLT SIZE Multifan 4E40 230 v. 16” Multifan 2E20 8” Multifan 4E35 230 v 14” Multifan 4E40 115 v. 16” Multifan 4E45 115 v. 18” Multifan 4E50 115 v. 20” Multifan 4E50 230 v. 20”...
APPENDIX TROUBLESHOOTING SYMPTOM CAUSE and REMEDY − Lo is Temperature is below minimum 42.0°F continually ° (5.5 − displayed Probe is disconnected or defective. − Hi is Temperature is above maximum 111°F continually (42°C). − displayed Probe is short circuited. −...
Limited Warranty manufacturered equipment supplied components have gone through rigorous inspection to assure optimal quality of product and reliability. Individual controls are factory tested under load, however the possibility of equipment failure and/or malfunction may still exist. For service, contact your local retailer or supplier. The warranty period shall be for two years from manufacturing date.
Page 48
MAV ECS4+ V2.1 July 2001 www.monitrol.com...