System Mode Settings

(POS 7)

No Stage Position Summer NOStS
This parameter is used to set the position the inlet will take when no
ventilation stages are activated and the Outside Temperature is equal to
or above Summer Temp. When the Outside Temperature is lower than
Summer Temp, but greater than Winter Temp, the position the inlet will
take when no ventilation stages are activated will modulate according to this
setting and No Stage Position Winter. This parameter will appear only if at
least one of the units connected to the DIP-1C uses an outside temperature
probe. This parameter is adjusted in 1% increments from 0% to 100%.
No Stage Position NOStg
This parameter is used to set the position the inlet will take when no
ventilation stages are activated and the Outside Temperature is not used.
This parameter will appear only if none of the units connected to the DIP-1C
use an outside temperature probe. This parameter is adjusted in 1%
increments from 0% to 100%.
No Stage Position Winter NOStW
This parameter is used to set the position the inlet will take when no
ventilation stages are activated and the Outside Temperature is equal to
or below Winter Temp. When the Outside Temperature is lower than
Summer Temp, but greater than Winter Temp, the position the inlet will
take when no ventilation stages are activated will modulate according to this
setting and No Stage Position Summer. This parameter will appear only if
at least one of the units connected to the DIP-1C uses an outside
temperature probe. This parameter is adjusted in 1% increments from 0% to
100%.

(POS 8)

Inlet Alarm Option ALOPT
This parameter is used to determine if the alarm relay will activate when the
inlet's potentiometer is defective. If this parameter is set to
alarm relay will activate when the inlet's potentiometer is defective. If this
parameter is set to
potentiometer is defective.

(POS 9)

Display Language LANG
This parameter is used to select the language used by the DIP-1C. If this
parameter is set to
If this parameter is set to
language.
Section C-30
OFF, the alarm relay will not activate when the inlet's
ENG, the configuration will use the English language.
FrA, the configuration will use the French
www.monitrol.com