ITT PumpSmart PS220 Configuration And Operation Manual page 46

Hide thumbs Also See for PumpSmart PS220:
Table of Contents

Advertisement

PS220 Configuration & Operation Guide
4. The software automatically defines the selected analog input to "PROC TRANS 1" as the primary process
transmitter for the system.
5. Configure the Setpoint limits.
The setpoint limits, SETPOINT MIN and SETPOINT MAX, are the values, below and above, that the system
cannot be operated at. These can be different from the scaled values configured for use. These limits can
prevent incorrect low and high setpoints from being used by the system.
If the process variable chosen is SmartFlow or SmartTDH, then only SETPOINT MIN and SETPOINT MAX are
shown and need to be defined. SETPOINT MIN will typically be zero while SETPOINT MAX should be set at
a value equal to the maximum flow or TDH of the pump. Be sure that you complete the SmartFlow wizard
prior to running your process or the feedback will be incorrect.
5.1. Configure the Setpoint Min
5.2. Configure the Setpoint Max:
45 PS220
1. "ARROW RIGHT" to change
2. "ARROWS" to change value
3. "Save"
4. "ARROW DOWN"
1. "ARROW RIGHT" to change
2. "ARROWS" to change value
3. "Save"
4. "Next"

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PumpSmart PS220 and is the answer not in the manual?

Table of Contents

Save PDF