PS220 Configuration & Operation Guide
4. The software automatically defines the selected analog input to "PROC TRANS 1" as the primary process
transmitter for the system.
5. Configure the Setpoint limits.
The setpoint limits, SETPOINT MIN and SETPOINT MAX, are the values, below and above, that the system
cannot be operated at. These can be different from the scaled values configured for use. These limits can
prevent incorrect low and high setpoints from being used by the system.
If the process variable chosen is SmartFlow or SmartTDH, then only SETPOINT MIN and SETPOINT MAX are
shown and need to be defined. SETPOINT MIN will typically be zero while SETPOINT MAX should be set at
a value equal to the maximum flow or TDH of the pump. Be sure that you complete the SmartFlow wizard
prior to running your process or the feedback will be incorrect.
5.1. Configure the Setpoint Min
5.2. Configure the Setpoint Max:
45 PS220
1. "ARROW RIGHT" to change
2. "ARROWS" to change value
3. "Save"
4. "ARROW DOWN"
1. "ARROW RIGHT" to change
2. "ARROWS" to change value
3. "Save"
4. "Next"