PS220 Configuration & Operation Guide
99.06
MOTOR NOMINAL CURRENT
99.07
MOTOR NOMINAL VOLTAGE
99.08
MOTOR NOMINAL FREQUENCY
99.09
MOTOR NOMINAL SPEED
99.10
MOTOR NOMINAL POWER
99.16
Motor Phase Order
99.XX
Refer to the ABB ACS880 Firmware
Parameters
manual
not shown
281 PS220
Defines the nominal motor current. Must be equal to the value on the motor rating plate.
If multiple motors are connected to the drive, enter the total current of the motors.
Notes:
• Correct motor operation requires that the magnetizing current of the motor does
not exceed 90% of the nominal current of the drive.
• This parameter cannot be changed while the drive is running.
Defines the nominal motor voltage supplied to the motor. This setting must match the
value on the rating plate of the motor. This parameter cannot be changed while the drive
is running.
Defines the nominal motor frequency. This setting must match the value on the rating
plate of the motor.
This parameter cannot be changed while the drive is running.
Defines the nominal motor speed. The setting must match the value on the rating plate of
the motor.
This parameter cannot be changed while the drive is running.
Defines the nominal motor power. The setting must match the value on the rating plate
of the motor. The unit is selected by parameter 96.16, Unit selection. This parameter
cannot be changed while the drive is running.
Define how the drive fires the IBGT for the output phase of the motor. Choices are :
UWV
UVW. Used to correct Motor rotation.
Reference the ABB ACS880 Firmware Manual for parameter definition. All ACS880
parameters may not be supported.