PS220 Configuration & Operation Guide
GROUP 80
CONDITION MONITORING
80.01
CONDITION STATUS
80.04
COND 1 SOURCE
COND 1 WRN LIM HI
80.05
COND 1 WRN LIM LO
80.06
COND 1 ALARM
80.07
COND 1 ALRM LIM HI
80.08
COND 1 ALRM LIM LO
80.09
COND 2 SOURCE
80.10
COND 2 WRN LIM HI
80.11
131 PS220
DESCRIPTION
A 1 indicates the condition is active
BIT
FUNCTION DESCRIPTION
0
Enabled
1
Cond1 High Alarm
2
Cond1 High Warning
3
Cond1 Low Warning
4
Cond1 Low Alarm
5
Cond2 High Alarm
6
Cond2 High Warning
7
Cond2 Low Warning
8
Cond 2 Low Alarm
13
Sleep Active
14
Min Speed Active
None [Default]
Select the source of the signal to be monitored. The
source can either be from an external transmitter wired
Flow Actual
to an available analog input or it can be an internal
Pressure Actual
signal as selected by the parameter number.
Level Actual
Speed
Torque
Power
Current
Temperature
Actual
SmartFlow
PROC TRANS 1
PROC TRANS 2
The high value of the warning limit. A warning
-10000 to +10000
occurs if the monitored signal rises above this
0 [default]
value for longer than the response delay
Inactive if set to 0.
The low value of the warning limit. A warning
-10000 to +10000
occurs if the monitored signal drops below this
0 [default]
value for longer than the response delay. Inactive if
set to 0.
DISABLED [default]
Protection is inactive.
ALARM ONLY
Selecting ALARM ONLY will issue a Keypad
message showing that an ALRM LIM HI or ALRM LIM
LO condition is detected. No further action is
taken.
Selecting MIN SPD will issue a Keypad message
MIN SPD
showing that an ALRM LIM HI or ALRM LIM LO
condition is detected and will drop to MIN SPEED.
If the alarm does not reset itself after the MIN SPD
STP DLY the PS220 will fault.
The PS220 will shut down and go into a sleep mode
SLEEP
if an ALRM LIM HI or ALRM LIM LO condition is
detected. It will "wake up" according to the value
in 80.22.
FAULT
The PS220 faults if an ALRM LIM HI or ALRM LIM LO
condition is detected. A Keypad notice is issued
The high value of the alarm limit. An alarm occurs if the
-10000 to +10000
monitored signal rises above this value for longer
0 [default]
than the condition response delay (par 80.16).
Inactive if set to 0.
The low value of the alarm limit. An alarm occurs if the
-10000 to +10000
monitored signal drops below this value for longer
0 [default]
than the response delay (par 80.16). Inactive if set
to 0.
None [Default]
Select the source of the signal to be monitored.
The source can either be from an external transmitter
Flow Actual
wired to an available analog input or it can be an
Pressure Actual
internal signal as selected by the parameter
Level Actual
number.
Speed
Torque
Power
Current
Temperature Actual
SmartFlow
PROC TRANS 1
PROC TRANS 2
The high value of the warning limit. A warning occurs
-10000 to +10000
if the monitored signal rises above this value for
0 [default]
longer than the response delay (par 80.16). Inactive
if set to 0.