SICK DL100 Pro PROFIBUS DP Operating Instructions Manual

SICK DL100 Pro PROFIBUS DP Operating Instructions Manual

Hide thumbs Also See for DL100 Pro PROFIBUS DP:
Table of Contents

Advertisement

Quick Links

O P E R A T I N G I N S T R U C T I O N S
DL100 Pro PROFIBUS DP
Distance sensor

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DL100 Pro PROFIBUS DP and is the answer not in the manual?

Questions and answers

Summary of Contents for SICK DL100 Pro PROFIBUS DP

  • Page 1 O P E R A T I N G I N S T R U C T I O N S DL100 Pro PROFIBUS DP Distance sensor...
  • Page 2 Original document This document is an original document of SICK AG. O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK...
  • Page 3: Table Of Contents

    Received signal level................Electrical installation................ 30 8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 4 Configuring and parameterizing nodes........10.2 GSD modules.................... O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK Subject to change without notice...
  • Page 5 13.1 Optics......................13.2 Performance data..................13.3 Supply......................8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 6 15.1 Menu structure..................15.2 Declarations of conformity and certificates..........O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK Subject to change without notice...
  • Page 7: About This Document

    … highlights useful tips and recommendations as well as information for efficient and trouble-free operation. 8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 8: Scope Of Delivery

    Other publications related to the devices described here • Publications dealing with accessories O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK Subject to change without notice...
  • Page 9: Safety Information

    Use of unauthorized spare parts, consumables, and accessories ■ 8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 10: Modifications And Conversions

    O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK...
  • Page 11: Warning Signs On The Device

    A class 2 laser is installed in the device. The housing is labeled with a warning sign. 8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 12: Ul Conformity

    Caution – Use of controls or adjustments or performance of procedures other than those specified herein may result in hazardous radiation exposure. O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK...
  • Page 13: Function And Use

    8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 14: Type Label

    The status of the device and the status of all interfaces is displayed by LEDs in accordance with the following table. O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK...
  • Page 15: Display

    This operating mode enables you to display other process values. 8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 16: Operating Pushbuttons

    Jump back to the next highest menu level or to the measured value display. ■ O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK...
  • Page 17: Transport And Storage

    8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 18: Mounting

    +1° … +3° in one of the 2 axes (horizontal or vertical). O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK...
  • Page 19 7, page 8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 20 Tilt of approx. 1° to 3° Shiny surface suchas a rail O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK...
  • Page 21: Placement Of Multiple Distance Sensors

    . This applies to mounting with light beams in both the same and opposite directions. 8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 22 Reflector Minimum distance Maximum travel distance O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK Subject to change without notice...
  • Page 23: Arranging The Distance Sensor To The Adjacent Optical Data Transmission System

    Formula: a ≥ 0.0083 x s 8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 24: Assignment To Isd300, Isd400-1Xxx Or Isd400-6Xxx

    The maximum measurement distance and variant of the distance sensor does not have an impact on the minimum distance. O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK...
  • Page 25: Mounting The Alignment Bracket And Distance Sensor

    Mount the alignment bracket using the four slotted holes with the supplied screws. 8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 26 Secure the star grip screw in place using a knurled nut. Knurled nut O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK...
  • Page 27: Aligning The Distance Sensor And Reflector With Each Other

    M5 hex socket adjustment screw for aligning the distance sensor in the Y-direction 8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 28: Received Signal Level

    Figure 15: Signal attenuation depends on the distance between device and reflector Typical signal attenuation O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK...
  • Page 29 Signal damping in dB Distance in m 8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 30: Electrical Installation

    O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK...
  • Page 31 Figure 18: Alternative laying – Separate cables with metallic separators 8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 32: Connecting The Device Electrically

    MF1, MF2 supply voltage connection diagram Figure 21: MF1, MF2 supply voltage connection diagram O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK...
  • Page 33: Ethernet Connection Diagram

    – Data signal + – – 8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 34: Profibus Out Connection Diagram

    "PROFIBUS OUT connection diagram", page 34 on the distance sensor. O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK Subject to change without notice...
  • Page 35: Operation

    "Warning messages", page 8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 36: Swvers Menu

    1 ... 125 Factory setting • O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK Subject to change without notice...
  • Page 37: More? Menu

    In the more? menu, you can activate or deactivate the advanced menu view. 8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 38: Mfx On Menu

    Factory setting • ActLow O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK Subject to change without notice...
  • Page 39: Mf1 - Dist Submenu

    ■ Functn parameter: Dist option ■ 8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 40: Mf1 - Speed Submenu

    Menu MFx On: Enable option • Functn parameter: Speed option O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK Subject to change without notice...
  • Page 41: Mf1 - Srvice Submenu

    Menu MFx On: Enable option • Functn parameter: Srvice option 8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 42: Mf1 - Lsroff Submenu

    LsrOff. If MF1 is active, the laser diode is switched off. O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK...
  • Page 43: Mf1 - Preset Submenu

    The output value of the device corresponds to the set value for Preset at the initialization position. 8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 44: Mf2 Menu

    Requirement for display: • more? menu: Yes option O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK Subject to change without notice...
  • Page 45: Specfu Menu

    - (negative direction) Factory setting • 8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 46: Performing A Reset

    Press the pushbutton to terminate the process. O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK Subject to change without notice...
  • Page 47 8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 48: Ethernet Interface

    It may be necessary to reset to factory settings and restart the device. O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK...
  • Page 49: Sopas Et Configuration Software

    User information windows or a firmware update) . 8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 50: Firmware Update

    ✓ Successful transmission of the new firmware is displayed. O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK Subject to change without notice...
  • Page 51 Update device driver via upload from the device. 8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 52 Firmware update and update of the device in the SOPAS project are complete. O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK...
  • Page 53: Profibus Interface

    PROFIBUS network. Every device receives an ID number from the PROFIBUS and PROFINET user organization (PI). 8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 54: Reading In Generic Station Description (Gsd)

    GSD file. O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK...
  • Page 55: Module Types And Module Naming

    Module 13 consists of three values: 8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 56: Module Overview

    2 words Speed Input 2 words O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK Subject to change without notice...
  • Page 57 Service hours [10 h] Input 2 bytes 8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 58 [MF2 Service] Heating Parameter off/on Status O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK Subject to change without notice...
  • Page 59: Module Description

    This module reads the current distance value. 8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 60: Module 2: Distance/I1W

    O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK...
  • Page 61: Module 3: Speed/I2W

    Signed 32-bit number in two´s complement 8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 62: Module 4: Distance/I2W, Speed/I2W

    • Signed 32-bit number in two´s complement O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK Subject to change without notice...
  • Page 63: Module 5: Distance/I2W, Preset Dyn./O2W

    If bit 30 is set, the setting of bit 31 is ignored. 8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 64 Distance Resolution Factory setting • 0.1 mm O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK Subject to change without notice...
  • Page 65: Module 6: Time/I4W, Distance/I2W

    Type Input module, 8 words, consistent 8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 66 Distance Resolution Factory setting • 0.1 mm O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK Subject to change without notice...
  • Page 67: Module 10: Status/I2B, Control/O2B

    Type • 1 bit 8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 68 0.0 ... 0.7 Reserved Type • 1 bit O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK Subject to change without notice...
  • Page 69: Module 13: Temp/I1B, Level/I2B, Hrs/I2B

    • Disable Factory setting • enable 8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 70 Factory setting • both directions [+/-] O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK Subject to change without notice...
  • Page 71 Options • • Factory setting • 8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 72 Options • • Factory setting • O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK Subject to change without notice...
  • Page 73: Module 22: Setup Preset Static

    5. 8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 74: Module 23: Setup Offset

    O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK...
  • Page 75 –10 … +40 °C Factory setting • –10 °C 8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 76: Module 26: Setup Free Dist. Resolution

    This module is used to set the resolution of the speed value when using free Speed Resolution. O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK...
  • Page 77: Module 30: Serial No/I8B

    Module 32: Version HW/i8b Type Input module, 8 bytes 8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 78: Module 33: Version Fpga/I10W

    This module can be used to query the version number of the firmware of the application processor of the device. O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK...
  • Page 79: Module 35: Version Uc2/I10W

    8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 80 MF1 or a dynamic preset via module 5. O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP...
  • Page 81: Maintenance

    Recommended: At least every 6 months. 8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 82: Troubleshooting

    (meaning) NoWrn No warning O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK Subject to change without notice...
  • Page 83: Error Messages

    (meaning) NoErr No errors – 8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 84: Communication Problems

    PROFIBUS problems The BF/SF LEDs indicate the PROFIBUS status: O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK Subject to change without notice...
  • Page 85: Returns

    Separate the recyclable materials by type and place them in recycling containers. ■ 8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 86: Technical Data

    Statistical error 1 σ, environmental conditions constant, minimum warm-up time 10 min. O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK...
  • Page 87: Supply

    -20 ... +75 °C (with cooler housing TPCC) 8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 88: Structural Design

    6-digit with a 5 x 7 dot matrix ■ O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK Subject to change without notice...
  • Page 89: Dimensional Drawing

    Electrical connection Display and control elements 8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 90: Accessories

    Part number 2058653 Material Galvanized sheet steel O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK Subject to change without notice...
  • Page 91: Cooler Housing

    IP55 (horizontal mounting) IP54 (vertical mounting) 8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 92: Annex

    Interface Multifunctional input/multifunctional outputs Indication only O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK Subject to change without notice...
  • Page 93 The menu displayed depends on the selected function (Functn) see D ß 8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 94 For the variants DL100-xxHxxxxx only á O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP 8014755/19H8/2021-10-15 | SICK Subject to change without notice...
  • Page 95: Declarations Of Conformity And Certificates

    The declarations of conformity and certificates can be downloaded from the Internet at: • www.sick.com/DX100 8014755/19H8/2021-10-15 | SICK O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP Subject to change without notice...
  • Page 96 E-Mail office@sick.com.gr E-Mail info@sick.ru Vietnam Hong Kong Singapore Phone +65 6744 3732 Phone +852 2153 6300 Phone +65 6744 3732 E-Mail sales.gsg@sick.com E-Mail ghk@sick.com.hk E-Mail sales.gsg@sick.com Detailed addresses and further locations at www.sick.com SICK AG | Waldkirch | Germany | www.sick.com...

This manual is also suitable for:

8014755

Table of Contents