Endress+Hauser Proline Prosonic Flow B 200 Operating Instructions Manual page 15

Ultrasonic flow measuring system
Hide thumbs Also See for Proline Prosonic Flow B 200:
Table of Contents

Advertisement

Proline Prosonic Flow B 200
Two-path version: DN 100 to 200 (4 to 8")
A
1
10 × DN
C
1
10 × DN
å 4
Two-path version: minimum inlet and outlet runs with various flow obstructions
A
90 ° elbow or T-section
B
Pump
C
2× 90 ° elbow 3-dimensional
D
Control valve
1
Inlet run
2
Outlet run
6.1.2
Requirements from environment and process
Ambient temperature range
Measuring device
Local display
If operating outdoors:
Avoid direct sunlight, particularly in warm climatic regions.
System pressure
Sensor
Max. 10 bar (145 psi)
Thermal insulation
For optimum temperature and methane fraction measurement (order characteristic for "Sensor
version", option 2), make sure that heat is neither lost nor applied to the sensor. Thermal
insulation can ensure that such heat transfer does not take place.
Thermal insulation is particularly recommended in situations where there is a large difference
between the process temperature and the ambient temperature. This can result in heat
Endress+Hauser
2
3 × DN
2
3 × DN
–40 to +60 °C (–40 to +140 °F)
–20 to +60 °C (–4 to +140 °F), the readability of the display may be impaired at
temperatures outside the temperature range.
B
1
10 × DN
D
1
10 × DN
Mounting
2
3 × DN
2
3 × DN
A0015553
15