Operating Data - JUMO EM Series Operating Manual

Hide thumbs Also See for EM Series:
Table of Contents

Advertisement

7 Technical data
7.5

Operating data

Switching differential in %
of control range/limit value range
Switching function
TR, TW
STW (STB)
Sequence contact gap on multi-
pole versions
Switching point accuracy in %
of control range/limit value range
Switching function
TR
TW
TB
STW (STB)
32
Measuring system
Liquid-filled
Nominal
Possible actual
value
value
2.5
Approx. 2.5 to 3.5 5
5
Approx. 5 to 6
7
Approx. 7 to 8
1
Approx. 1 to 2
5
Approx. 5 to 7
Switching
Sequence contact gap relative to
differential
scale range
Minimum
1 %
1 %
2.5 %
1 %
3 %, 5 %
2 %
6 %, 7 %, 10 % 3 %
The sequence contact gap can be specified in °C in relation to the setpoint of
contact I.
(The contact track no. is stamped on the back of the housing par.)
Prefix - = switching before reaching the setpoint value
Prefix + = switching after reaching the setupoint value
For the synchrozized version, specify "0" as the sequence contact gap.
Switching differential
Liquid-filled
1 %, 2.5 %
5 %
7 %
1 %, 2.5 %
5 %
7 %
-
See table for control ranges and probes
Gas-filled
Nominal
Possible actual
value
value
Approx. 5 to 11
6
Approx. 6 to 14
10
Approx. 10 to 16
3
Approx. 2.5 to 4
6
Approx. 6 to 16
Maximum
According to control
range table
In the upper third of the scale or
limit value
Gas-filled
-
±1.5 %
3 %, 5 %
±3 %
6 %, 10 %
±4 %
-
±1.5 %
3 %, 5 %
±3 %
6 %, 10 %
±4 %
-
+0 %
-5 %
Standard
Upon request
Upon request
Extra cost
Standard
Switching point accuracy
of the sequence contact
gaps from the scale range
≤ 1 %
≤ 1 %
≤ 1 %
≤ 1 %