Technical Data; Control Ranges And Temperature Probes; Capillary And Temperature Probe - JUMO ATH-SE Series Operating Manual

Surface-mounting thermostats
Hide thumbs Also See for ATH-SE Series:
Table of Contents

Advertisement

7

Technical data

7 Technical data
7.1

Control ranges and temperature probes

Type
ATH.-SE-2
ATH.-SE-20
ATH.-SE-70
7.2

Capillary and temperature probe

Type
ATH.-SE-2
ATH.-SE-20
ATH.-SE-70
Capillary length
Min. bending radius of the capillary 5 mm
22
Control/limit
max. admissible
value ranges
excessive probe
temperature
°C
°C
0 to 100
125
20 to 90
125
30 to 110
135
20 to 120
140
60 to 140
165
20 to 150
175
50 to 200
230
50 to 250
290
50 to 300
345
30 to 110
135
60 to 140
165
20 to 150
175
50 to 250
290
50 to 300
345
Scale limit value
Capillary
≤ 200 °C
Copper (Cu)
Ø 1.5 mm
Material no. 2.0090
> 200 °C
Copper (Cu)
Ø 1.5 mm
Material no. 2.0090
all areas
Stainless steel (CrNi)
Ø 1.5 mm
1000 mm, max. 2000 mm as standard
Length of the temperature probe
in mm
Copper (Cu)
Stainless steel (CrNi)
Ø 6
Ø 8
Ø 6
107
75
99
138
91
130
125
84
117
107
75
99
123
83
117
88
65
80
101
72
93
-
-
73
-
-
63
112
78
104
110
77
102
80
61
72
-
-
66
-
-
58
Temperature probe
Copper (Cu)
Material no. 2.0090
hard soldered
Stainless steel (CrNi)
Material no. 1.4571
hard soldered
Stainless steel (CrNi)
Material no. 1.4571
welded
Ø 8
67
83
76
67
76
57
64
54
49
70
68
53
50
-

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ath-se-2Ath-se-20Ath-se-70

Table of Contents