JUMO EM Series Operating Manual page 33

Hide thumbs Also See for EM Series:
Table of Contents

Advertisement

Mid ambient temperature influence Deviation of the ambient temperature at the switching head and/or capillary
For temperatures with scale limit
value/limit value
Switching differential in %
Ambient temperature influence
on the switching head in %/°C
Ambient temperature influence
on the capillary in %/m
Temperature compensation (TK)
Temperatures
Admissible storage temperature
Admissible ambient temperature
for use
Nominal position (NL)
Operating medium
Time constant t
0.632
In water
In oil
In air or superheated steam
Mode of operation
TR, TW
TB
STW (STB)
STB
from the 22 °C calibration ambient temperature produces a switching point off-
set.
Higher ambient temperature = low switching point
Lower ambient temperature = higher switching point
TR, TW, TB
STW,
STB
< 200 °C
1/2.5 5
7
7/-
0.15
0.26
0.34 0.43
0.05 · °C · m 0.09 · °C · m 0.09 · °C · m 0.07 · °C· m 0.05 · °C · m
For detailed information see diagram.
-50 to +50 °C
80 °C max.
Any
Water, oil, air, superheated steam
≤ 45 s
≤ 60 s
≤ 120 s
According to EN 60730-1, DIN EN 60730-2-9, DIN EN 14597
2 BL
2 BFHLPV
2 BKLNP
2BFHKLNPV
Declaration:
2
Mode of operation type 2
B
Automatic mode of operation with micro disconnection
F
Only adjustable with tool
H
Release mechanism whose contacts can not be prevented from opening
K
With probe break protection
L
No auxiliary energy required
P
Mode of operation type 2, tested by declared temperature changes
V
Lockout
7 Technical data
TR, TW, TB
STW, STB
≥ 200 °C ≤ 350 °C
1/2.5 5
7/-
0.12
0.21
0.35
TR, TW, TB, STW,
STB
≥ 400 °C ≤ 500 °C
3/5
6
10
0.12
0.17
0.24
33

Hide quick links:

Advertisement

Table of Contents
loading