Technical data

7.1

Control ranges and probe table

For TR, TW, TB – liquid-filled
Control
Switch-
range/limit
ing differ-
value range
ential
°C
%
-20 to +40
1
2.5
5
7
0 to 50
1
2.5
5
7
20 to 90
1
2.5
5
7
0 to 100
1
2.5
5
7
30 to 110
1
2.5
5
7
0 to 150
1
2.5
5
0 to 200
1
2.5
50 to 200
1
2.5
50 to 250
1
2.5
5
50 to 300
1
2.5
For TR, TW, TB – gas-filled
Control
Switch-
range/limit
ing differ-
value range
ential
°C
%
20 to 400
5
10
20 to 500
3/5
6
10
Max. probe
Max. switch-
temperature
ing head
temperature
°C
°C
50
50
50
95
100
60
60
60
105
110
115
80
115
140
175
125
80
125
165
200
135
80
135
170
200
173
80
173
200
230
80
230
230
80
230
288
80
288
300
345
80
345
Max. probe
Max. switch-
temperature
ing head
temperature
°C
°C
460
80
500
575
80
Max. capillary
Max.
length
sequence
contact gap
in mm
K
5000
5
8
25
50
5
10
25
50
7
14
35
70
10
20
50
100
8
16
40
80
15
30
75
20
40
15
30
20
40
100
25
50
Max. capillary
Max.
length
sequence
contact gap
in mm
K
5000
75
200
1000
48
5000
95
5000
250
7 Technical data
Probe length "L",
probe Ø "d"
in mm
Ø 6 (Standard)
245
245
138
103
283
283
159
117
210
210
121
91
157
157
94
73
188
188
110
84
113
113
72
113
139
105
105
64
87
Probe length "L",
probe Ø "d"
in mm
Ø 6 (Standard)
237
127
278
276
95
Ø 8
145
145
91
73
165
165
101
80
127
127
82
67
100
100
68
58
116
116
76
63
78
78
57
78
92
70
70
49
61
Ø 8
137
81
158
106
65
29