Limits Per H1 Channel; General Maximum Limits - ABB LD 800HSE Manual

Table of Contents

Advertisement

Limits per H1 Channel

Limits per H1 Channel

General Maximum Limits

Maximum Limits per H1 Channel
Connections (VCRs) - overall
LAS schedules
Sub-schedules
Sequences per sub-schedule
Elements per sequence
Size of LAS schedule domain [octets]
(1) The total number of Source/Sink, Client/Server, and Publisher/Subscriber VCRs
in an H1 channel cannot exceed this value.
(2) As the LD 800HSE does not generate alarms, there is no practical use case for
Source VCRs.
Note, that the total size of the LAS schedule domain must not exceed 2000 octets.
Additionally for each component of the LAS schedule, the maximum value given in
the table applies.
The ABB configuration tools Fieldbus Builder FOUNDATION Fieldbus and
Control Builder F will automatically take into account these limits.
98
(2)
- Source
+ Sink
- Client + Server
- Publisher + Subscriber
Appendix B Limits and Performance Data
(1)
128
20
40
100
2
4
64
4
2000
3BDD011677-600 A

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ld 800hse ex

Table of Contents