Section 3 Configuration
To enable Control Builder F to do the configuration and commissioning of linking
devices of type LD 800HSE, this HSE device type has to be imported to the
engineering tool. For this purpose you will need the capabilities file (a file with the
extension .cfh) that is included on the Media CD-ROM LD 800HSE or is available
for download in the ABB SolutionsBank.
Additional information, firmware, and capabilities files for this product are
available in the ABB SolutionsBank. For details refer to
Installation.
Prerequisites for doing the plant configuration with Fieldbus Builder
FOUNDATION Fieldbus / Control Builder F are
In the Fieldbus Builder FOUNDATION Fieldbus / Control Builder F the IP address
set on the linking device has to be entered. It is used for identifying the linking
device, and forms the basis for all the connection-based communication with the
linking device.

Using a Redundant Set of Linking Devices

In the case of a redundant set of linking devices also the IP address of the second
physical linking device has to be entered.
When the two linking devices forming a redundant set are powered, the serial
link must be present. If the serial link is missing while the devices are powered,
both devices will behave like independent, non-redundant Primary Devices.
3BDD011677-600 A
a valid IP configuration of the linking device as described in
Update
on page 65 and
a physically commissioned linking device according to the commissioning
steps listed in
Commissioning the Hardware
Using a Redundant Set of Linking Devices
Section 2, Hardware
on page 44.
Firmware
73