Omron F3SG-RA Manual page 16

Safety light curtain
Hide thumbs Also See for F3SG-RA:

Advertisement

Standard Muting Mode/Exit-Only Muting Mode with two Muting Sensors using PNP Outputs
The following is the example of External Device Monitoring disabled, Auto Reset mode, PNP output and External Test in 24 V Active.
DIP Switch settings *5
EDM Disabled (factory default setting)
Receiver
Auto Reset (factory default setting)
PNP (factory default setting)
Emitter
External Test: 24 V Active (factory default setting)
Configure functions with the DIP Switches before wiring.
Wiring Example
F39-JG @ A-L
S1
Muting
Sensor
B1
A1
(PNP
output)
Reflector
S1: Test Switch (Connect the line to 0 V if this switch is not required)
S2: Lockout/Interlock Reset Switch,Override Switch or Override Cancel Switch
ML: Muting lamp
A1, B1: Muting sensor
Unblocked
Beam state
Blocked
Test Switch (S1)
MUTE A
MUTE B
OSSD
Function
F39-JG @ A-D
S2
*2
+24 VDC
Power Supply
0 VDC
DIP-SW1
DIP-SW2
2
ON
2
3
ON
3
4
ON
4
7
ON
7
4
ON
: Indicates a switch position.
ML
IN1
IN2
Safety
Controller *3 *4
*1.Also used as Override input line.
*2.Make sure to connect an override cancel switch to the Reset
line when using the override function. Otherwise the override
state may not be released by the override cancel switch,
resulting in serious injury.
*3.Refer to page 29 for more information.
*4.The safety controller and the F3SG-R must share the power
supply or be connected to the common terminal of the power
supply.
*5.The functions are configurable with DIP Switch. Refer to Safety
Light Curtain F3SG-R Series User's Manual for more information
on setting the functions by the DIP Switch.
F3SG-RA
ON
ON
ON
ON
15