Settings For Open-Vented Application; Screed Drying - REMEHA Quinta Ace 30 Service Manual

High-efficiency wall-hung gas boiler
Hide thumbs Also See for Quinta Ace 30:
Table of Contents

Advertisement

4 Installer instructions
4.7.4

Settings for open-vented application

4.7.5

Screed drying

Fig.24
Screed drying curve
50
35
T
20
2
0
0:00
0:00
0:00
10
9
4
d Number of days
T Heating set point temperature
1 Number of days on which the screed drying function
is activated (parameter CP470)
2 Screed drying start temperature (parameter CP480)
20
For this application, adjust the following parameter:
The screed drying function is used to force a constant flow temperature or
a series of successive temperature levels to accelerate screed drying on
underfloor heating.
1
0:00
0:00
0:00
8
7
6
5
1. Set parameter GP021 to the required temperature.
Tab.18
Increasing default ΔT setting
Boiler type
Quinta Ace 30
Quinta Ace 45
Quinta Ace 55
Quinta Ace 65
Quinta Ace 90
Quinta Ace 115
2. If a PWM-controlled central heating-pump is controlled by the boiler
control unit; set parameter PP014 to 2 °C.
1. Set parameter DP006 to 0,0 bar.
2. Set parameter GP021 to 20°C.
Important
The settings for these temperatures must follow the screed
layer's recommendations.
Activation of this function via the parameter CP470 forces the
permanent display of the screed drying function and deactivates
all other regulator functions.
When the screed drying function is active on one circuit, all
other circuits and the domestic hot water circuit continue to run.
It is possible to use the screed drying function on circuits A and
B. The parameter settings must be made on the PCB that
controls the circuit concerned.
0:00
0:00
0:00
4
3
2
d
3 Screed drying stop temperature (parameter CP490)
4 Start of the screed drying function
5 End of the screed drying function, back to normal
running
Important
Every day at midnight, the screed drying start temperature set
point is recalculated and the remaining number of days on which
the screed drying function is running decreases.
Default ΔT setting
Maximum ΔT setting
25 °C
40 °C
20 °C
35 °C
3
0:00
0:00
0:00
1
x
x
5
7703943 - v.06 - 13122021
0:00
AD-3001406-01