Wiring
3.1.2
Wire the core processor to the sensor using shielded
cable
Prerequisites
For hazardous area installations, shielded cable must be installed with cable glands at the
core processor end. Cable glands that meet hazardous area requirements can be
purchased from Micro Motion. Cable glands from other vendors can be used.
CAUTION!
Procedure
1.
10
Figure 3-2:
Enhanced core processor terminals
A. Brown
B. Violet
C. Yellow
D. Orange
E. Gray
F. Blue
G. White
H. Green
I.
Red
J.
Ground screw (black)
Sensor wiring is intrinsically safe. To keep sensor wiring intrinsically safe, keep the
sensor wiring separated from power supply wiring and output wiring.
Keep cable away from devices such as transformers, motors, and power lines, which
produce large magnetic fields. Improper installation of cable, cable gland, or conduit
could cause inaccurate measurements or flow meter failure.
Improperly-sealed housings can expose electronics to moisture, which can cause
measurement error or flowmeter failure. Install drip legs in conduit and cable, if
necessary. Inspect and grease all gaskets and O-rings. Fully close and tighten all housing
covers and conduit openings.
Identify the components of the cable gland and cable.
J
A
B
C
Micro Motion Liquified Natural Gas Meter
I
H
G
F
E
D