Connecting the Power

The IOLM provides M12 (5-poles) L-coded input and output power connectors. Use a 24VDC power
supply capable of the total output current required.
Note: Power connectors must have an approved cable or protective cover attached to the port
guarantee to IP67 compliance. If you require cables or protective covers, see the Emerson website.
Figure 5: IOLM Power Connectors Pinout
Pin
1
2
3
4
5
Note: The IOLM requires a UL-listed power supply with an output rating of 24VDC.
Power Supply In - Maximum V
† V
You can use the following procedure to connect the IOLM to a power supply.
Note: Power should be disconnected from the power supply before connecting it to the IOLM.
Otherwise, your screwdriver blade can inadvertently short your power supply terminal connections to
the grounded enclosure.
Configuring
Power Input
Power Output or Actuator
(Male)
V
+
S
V
-
A
V
-
S
V
+
A
Power Supply
IO-Link Connector Port 1
C/Q (Pin 4)
L+/L- Sensor Supply (Pins 1 and 3)
IO-Link Connector Port 3
C/Q (Pin 4)
L+/L- Sensor Supply (Pins 1 and 3)
IO-Link Connectors Ports 2 and 4 - 8
C/Q (Pin 4)
L+/L- Sensor Supply (Pins 1 and 3)
IOLM Power
Power Supply Out
V
S
V
A
output available is determined by subtracting the following from the available input
S
IO-Link Master module electronics current.
Total L+/L- current for all IO-Link ports.
Total C/Q current for all IO-Link ports.
††
V
output available is the same as the available U
A
Power (Female)
V
+ or +V
S
V
- or 0V
A
V
- or 0V
S
V
+ or +V
A
FE
V
S and
A
200 mA (Maximum) 1.6 A (Maximum)
200 mA (Maximum) 1 A (Maximum)
500 mA (Maximum)/up to 1A Output Budget
Note: See IOLM Hardware Installation for
information about how to divide up the power
current.
Description
IO-Link Master's system electronics and IO-
Link devices
Actuator supply
IO-Link Master's system electronics and IO-
Link devices
Actuator supply
Values
16A (Maximum)
200 mA (Maximum)
output between ports.
100 mA @ 24 VDC (U
S
16A
(Maximum)
††
16A
(Maximum)
input current.