Fault Rectification - EMS SmartCell Programming Manual

Intelligent wireless zone monitor
Hide thumbs Also See for SmartCell:
Table of Contents

Advertisement

Fault rectification

Device type
Fault displayed
All device types
Battery Missing
WZM
Mains Fail
Detector
Head Fault
Detector
Head Dirty
All device types
Tamper
Open Circuit / Short Circuit
Input/output
All device types
Radio signal strength
No Signal Fault
All device types
Battery Low
WZM
Battery Supply Failure
All device types
Low signal
All device types
Good signal
Call point
Fire
Fire
Detector
©2020 EMS Ltd. All rights reserved.
Rectification process
Check all batteries are inserted correctly. Check voltage on
batteries. Replace batteries if necessary or re-insert correctly.
Check the mains supply to the unit.
It is recommended that the detection device be replaced due to
a fault with the head being reported.
Clean with compressed air if necessary, as the device is
reporting that the chamber is dirty. Check the device is in a
clean environment and is free from smoke, dust and dirt.
Check the device is assembled correctly.
Check the 20 kΩ end of line resistor is in place and that
connections are secure.
Check the devices location to ensure no visible cause can be
seen. Check that the device is still powered and has been added
to the system. (See the 'How to improve device signal levels'
section for more information).
Replace all device batteries with specified batteries - see the
associated device installation guide and replace within 30 days.
Check the integrity of the battery and it's connection.
Note: no fault will be indicated as communication is still taking
place, albeit at a low signal level. Check the device's location to
ensure there is no obvious cause. (See the 'How to improve
device signal levels' section for more information).
No action required.
Check the device's resettable element is correctly in place and
that the yellow area is not being displayed. If shown, reset the
device using the reset key.
Ensure that the environment in the device's location is free of
smoke, residue and dust.
Page 50 of 80
MK067-0001-99 (Issue 1) 04/11/2020 AJM

Hide quick links: