WZM to an Addressable Control Panel b) WZM to System 5000 Control Panel c) Remote WZM to System 5000 Control Panel, option 1 d) Remote WZM to System 5000 Control Panel, option 2 e) WZM to a Conventional Panel, option 1...
Introduction The EMS Wireless Zone Monitor (WZM) allows for 30 FireCell wireless devices to be added to an existing Fire Alarm Control Panel, in conjunction with an EMS Zone Interface Module (ZIM). Wireless Zone Zone Interface Monitor Monitor (WZM)
Step 2: Wiring a) WZM to an Addressable Control Panel Zone Wireless LOGON ANTENNA KEEP CABLES AWAY FROM THIS AREA 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 SERIAL NO RESET RADIO...
WZM to System 5000 Control Panel Zone Wireless LOGON ANTENNA KEEP CABLES AWAY FROM THIS AREA 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 SERIAL NO RESET RADIO Interface POWER Zone...
Remote WZM to System 5000 Control Panel, option 1 (when both sounders and detection are added to the WZM) Wireless Zone LOGON ANTENNA KEEP CABLES AWAY FROM THIS AREA 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7...
Remote WZM to System 5000 Control Panel, option 2 (when only sounders are added to the WZM) Wireless Zone LOGON ANTENNA KEEP CABLES AWAY FROM THIS AREA 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7...
WZM to a Conventional Panel, option 1 (providing fault noti cation on the sounder circuit) Zone Interface Monitor LOGON ANTENNA KEEP CABLES AWAY FROM THIS AREA SERIAL NO (ZIM) with Conventional Interface Card (CIC) tted CLOSED F-SAFE ENABLE...
WZM to a Conventional Panel, option 2 (providing fault noti cation on the zone circuit) LOGON ANTENNA Zone Interface Monitor KEEP CABLES AWAY FROM THIS AREA SERIAL NO (ZIM) with Conventional Interface Card (CIC) tted CLOSED F-SAFE ENABLE...
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 1 2 3 4 5 6 7 RADIO RESET The Rotary Control is used to navigate the WZM’s POWER menu structure. It can be pressed and released to HELP BACK...
www.acornfiresecurity.com Wireless Zone Monitor Menu Structure Front Screen Device Status Dev Address Fault Status Add New Device Alarm Status* Remove Device Battery Level Interface Status Signal Level Radio Channels Manual Update Ident Software Version Dev Address Type: ** Alarm Status shown as I/O Status for Input/Output Device types.
www.acornfiresecurity.com Step 3: Power Up the Devices Detectors, Sounders, Callpoints, Input/Output Units and the Zone Interface Module have power jumpers that power the device as shown: device device powered unpowered (both pins linked) (pins unlinked) Power jumper locations are shown below: Wireless Wireless Wireless...
Step 4: Log On the Devices Programming is achieved manually within the menu structure of the WZM. The EMS Zone Interface Module (ZIM) must be logged on before adding other wireless devices Note to the system. The Log On process is as follows:...
Page 15
www.acornfiresecurity.com Step 4: Log On the Devices (continued) Troubleshooting 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 RADIO RESET Turn the rotary control to change POWER the N? to Y? HELP BACK Add Dev A1B2C Y? FAULT ISOLATE Where: N? = NO...
www.acornfiresecurity.com Step 6: Check Signals The signal levels for all wireless devices can be viewed as follows: 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 RADIO RESET POWER From Front display: HELP BACK DEV18 AL00 FT00 FAULT ISOLATE...
Page 18
POWER screen will display the signal level HELP BACK Ch1 L1 D 100 FAULT received at the WZM from the ISOLATE device: 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 RADIO RESET Click the rotary control, and the...
Q; How do I replace a device on the system? A; To replace a device on the system, the device must rstly be removed from the WZM (see above). Then the new device must be added to the system. (See previous Step 3 Log On Devices) Q;...
WZM Fault Recti cation Fault symptoms seen at the WZM and their relevant recti cation processes are shown below: Device Type Symptom Recti cation Process Check device is inserted correctly into its base. All Device Types. In Tamper. Check all batteries are inserted correctly. Check voltage All Device Types.
This fault can occur for the following reasons: A - Faults on the WZM. B - The ZIM is not logged on to the WZM? Whilst the ZIM is not logged on, the ZIM’s default output state is energised. C - Check the wiring from the ZIM’s ‘Output 2’ to the Control Panels associated fault input.
/ electrical equipment near the unit, contrary to the device installation instructions? Are the signal levels ok now? Carry out a survey to re-check signal levels. Signal Levels Contact the EMS Technical successfully Support department improved. further advice. www.acornfiresecurity.com...