Pulsed Output - EMS SmartCell Programming Manual

Intelligent wireless zone monitor
Hide thumbs Also See for SmartCell:
Table of Contents

Advertisement

Pulsed output

As default, the pulsed output, for the fire and the fault relays, is set to latched. Upon an activation, the relay
will remain latched in alarm until the WZM is reset. This however can be changed to pulse into alarm for a
pre-defined period of time, before automatically clearing. Permitted times range from 5-60 seconds.
If the pulsed out is to be changed ,
the 'Access level 3' section for details), press the
until the screen displays:
Press the
button and the screen will display:
Press the
button until the screen will displays:
3
Press the
button and the screen will display:
Press the
button until the screen will displays:
3
Press the
button and the screen will display:
1
Press the
and
3
the required relay type:
In this example, the fault relay has been chosen.
Press the
button and the screen will display:
©2020 EMS Ltd. All rights reserved.
from access level 3 (refer to
buttons, until the screen displays
Page 41 of 80
View System Status
Maintenance/Test
button
3
Device Options
WZM Settings
Panel Type
Sounder Options
Device Indicator
Panel Type
Sounder Options
Device Indicator
Default Tone Select
Sounder Duration
Sounder Activation
Pulsed Output
Default Tone Select
Sounder Duration
Sounder Activation
Pulsed Output
Fire Relay-
Fault Relay- LATCH
Fire Relay-
Fault Relay- LATCH
Fault Relay
00
Secs
MK067-0001-99 (Issue 1) 04/11/2020 AJM
SYSTEM SETUP
LATCH
LATCH
LATCH
To Select