Actuating shaft
Fig. 8-2: Actuating shaft
1. Unscrew front cover and place a 4 mm
Allen key on the red actuating shaft.
2. Use the Allen key to turn the actuating
shaft:
Î Only turn counterclockwise for actuators
with fail-safe action.
Note
Turn only as far as the end position, which is
at the point where the torque-dependent limit
switch is activated.
Î Once the magnet has been released, the
spring mechanism pushes the actuator
stem back to the fail-safe position.
3. Remove Allen key and carefully refasten
the front cover.
EB 5724 EN
8.5 Operation using memory
pen
See u EB 6661.
The memory pen can be loaded with data
configured in TROVIS-VIEW and the config-
uration data transferred to one or several
devices of the same type and version.
Additionally, the data from the device can
be written to the memory pen. This allows
the configuration data to be simply copied
from one device and loaded onto other de-
vices of the same type and version.
Note
On inserting a memory pen that is empty or
that contains data from another type of
device or another version of the same device
into the serial interface port of the actuator,
the data from the actuator are uploaded to
the memory pen regardless of the status of
the memory pen and any other data on the
memory pen will be overwritten.