5 Installation

5.1 Installation conditions

Work position
If not described otherwise in the valve docu-
mentation, the work position for the control
valve is the front view looking onto the oper-
ating controls.
Mounting orientation
The control valve can be installed in the
pipeline in any desired position. However, a
suspended mounting position of the actuator
is not permissible (see Fig. 5-1).
The cable gland must not face upward after
installation.
0...90°
0...90°
Fig. 5-1: Mounting position
EB 5724 EN
The degree of protection IP 54 can only be
achieved up to device index .03 when the
actuator is installed in the upright position.
See the last two figures of the configuration
ID written on the nameplate for the device
index.
Risk of damage or malfunction due to
adverse weather conditions.
Î Do not install the actuator outdoors.

5.2 Preparation for installation

Before installation, make sure the following
conditions are met:
− The electric actuator with process control-
Proceed as follows:
Lay out the necessary material and tools to
have them ready during installation work.
Cover screws
The actuator housing cover is fastened using
TORX PLUS
Î To screw or unscrew the screws, the fol-
− TORX
− TORX PLUS
− Flat-blade screwdriver with 0.8 mm
!
Note
NOTICE
!
ler is not damaged.
screws, size 10IP.
®
lowing screwdrivers can be used:
T10
®
10IP
®
blade thickness and 4.0 mm blade width
Installation