Trovis 5724-3 (Form-Fit Attachment) - Samson TROVIS 5724-3 Mounting And Operating Instructions

Hide thumbs Also See for TROVIS 5724-3:
Table of Contents

Advertisement

Force-locking attachment with coupling nut,
e.g. to Type 3222 Valve
1
Actuator stem
2
Coupling nut
3
Handwheel (TROVIS 5724-3 only)
Fig. 5-3: Attaching actuator and valve
5.4.2
TROVIS 5724-3 (form-fit
attachment)
NOTICE
!
Crush hazard arising from moving parts
(actuator and plug stem).
Î Do not insert hands or finger into the
yoke while the valve is in operation.
EB 5724 EN
Form-fit attachment with stem connector, e.g.
with rod-type yoke on Series V2001 Valve
4
Rod-type yoke
5
Stem connector
6
Nut
1. Place the actuator on the yoke (4) and
fasten with the coupling nut (2).
Tightening torque
2. Place actuator with yoke on the valve
and tighten the nut (6).
Tightening torque
3. Pull plug stem until it reaches the actua-
tor stem or extend actuator stem using
the handwheel (3).
Installation
20 Nm
150 Nm
5-3