Occupancy sensor interface

Advertisement

E T C I n s t a l l a t i o n G u i d e
W A R N I N G :
Step 1:
Step 2:
Step 3:
C A U T I O N :
W
(
)
HITE
NEUTRAL
B
(120V)
LACK
B
(277V)
ROWN
OR
O
(
RANGE
ANTENNA
WIRELESS TO
OTHER DEVICES
N o t e :
Step 4:
N o t e :
For indoor use only! Must install in an electrical junction box
or wire way.
Locate the circuit breaker panel and turn off the power to the circuit.
Remove face plates and other hardware from the junction box, gaining
access to the high voltage wiring.
The UAPSO mounts to the junction box or panel with 1/2" (13mm)
threaded nipple.
The UAPSO has an orange external antenna that extends off one
end of the unit. Do not cut, cap, or connect this wire.
Y
(347V)
ELLOW
)
U
NISON
O
CCUPANCY
INTERFACE
Follow all local code requirements for terminating wiring. Notice
the harness wires on the controller unit are pre-stripped for your
installation convenience.
The UAPSO controller is provided with a wire harness that serves 120,
277 or 347VAC power requirements depending on the wires used for
installation. Refer to the wiring diagram above to connect power to the
controller.
a:
For 120VAC applications, connect the black wire to the line input
feed wire. For 277VAC applications, connect the brown wire to the
line input feed wire. For 347VAC applications, connect the yellow
wire to the line input feed wire.
Cut and tie back the unused line power wires. Follow all local code
requirements for tieing back unused wires.
b:
Connect the white wire to the incoming Neutral wire.