A M P 1 I N T E G R AT E D P O W E R A N D E N E R G Y I N S TA L L AT I O N I N S T R U C T I O N S
AMP1

Quick setup

To enter BACnet communication parameters
These instructions assume the meter is set to factory defaults.
If it has been previously configured, all optional values should
be checked.
repeatedly until SETUP screen appears.
1. Press
or
to get to the PASWD screen.
2. Press
3. Press
to move through the digits. Use the
to enter your password (the default is 00000).
Exit the screen to the right.
4. Use
or
buttons to select the parameter to configure.
5. If the unit has an RS-485 interface, the first Setup screen
is S COM (set communications).
a. Press
to go to the ADDR screen and through the address
digits. Use
or
to select the Modbus address.
to accept the value and go to the BAUD screen.
b. Press
Use
or
to select the baud rate.
c. Press
to go to the PAR screen. Use
the parity.
d. Press
to go back to the S COM screen.
6. Press
to go to the S CT (Set Current Transducer) Setup
screen. If this unit does not have an RS-485 port, this will be
the first screen.
a. Press
to go to the CT V screen. Use
voltage mode Current Transducer output voltage.
b. Press
to go to the CT SZ screen and through the digits.
Use
or
to select the CT size in amps.
c. Press
to accept the value and go back to the S CT screen.
7. Press
to go to the S SYS (Set System) Setup screen.
a. Press
to go to the SYSTM screen. Use
the System type (see wiring diagrams).
to go back to the S SYS screen.
b. Press
to go to the S PT (Set Potential
8. (Optional) Press
Transformer) screen. If PTs are not used, then skip this step.
a. Press
to go to the RATIO screen and through the digits.
Use the
or
buttons to select the Potential Transformer
step down ratio.
b. Press
to go back to the S PT screen.
For troubleshooting or service related questions, contact ABB at 800-782-8061 or at epis.component.support@abb.com
9. Press
a. Press
and through the digits. Use the
the Line to Line System Voltage.
b. Press
10. Use the
or
buttons
11. Check that the wrench is not displayed on the LCD.
a. If the wrench is displayed, use the
the ALERT screen.
b. Press
For full setup instructions, see the configuration instructions.
or
to select
or
to select the
or
to select
to go to the S V (Set System Voltage) screen.
to go to the VLL (or VLN if system is 1L-1N) screen
to go back to the S V screen.
button to exit the setup screen and then SETUP.
to go through the screens to see which alert is on.
or
buttons to select
or