ABB GE ReliaGear AMP1 Installation Instructions Manual page 14

Table of Contents

Advertisement

14
A M P 1 I N T E G R AT E D P O W E R A N D E N E R G Y I N S TA L L AT I O N I N S T R U C T I O N S
AMP1
User interface for setup
To Setup p. 1 "S PWR"
Back
SPLOS
Phase
Loss
Back
SDMND
Demand
Back
S DIS
Display
Units
SPASS
Back
Setup
Passwords
To Setup page 1 "S BAC"
For troubleshooting or service related questions, contact ABB at 800-782-8061 or at epis.component.support@abb.com
VOLTS
IMBAL
--------
--------
0.10
0.25
Next
INTRV
--------
6
SEC
5
--------
4
00900
3
2
Next
1
UNITS
--------
IEEE
IEC
Next
SETUP
RESET
--------
--------
00000
00000
Next
Set phase loss:
VOLTS - Phase Loss Voltage: The fraction of the system
voltage below which Phase Loss Alarm is on. For system
types with neutral, the Line to Neutral voltage is also
calculated and tested. If the System Voltage is 600 and the
fraction is set to 0.10, then the Phase Loss threshold will be
60 volts.
IMBAL - phase loss imbalance: The fractional difference
in Line to Line voltages above which Phase Loss Alarm is
on. For system types with neutral, the Line to Neutral
voltages are also tested. For system types 1+N (10) and 2
(11) , imbalance is not tested.
Set demand interval:
INTRV - The number of Sub-Intervals (1 to 6) in a
Demand Interval . Default is 1 (block demand).
SEC - Sub-Interval length in seconds. Default is
900 (15 minutes). Set to 0 for external sync-to-comms.
Set display units: +/- to switch between:
IEEE – VLL VLN W VAR VA Units.
IEC – U V P Q S Units.
Set passwords:
SETUP - The Password to enter the SETUP menu.
RESET - The Password to enter the RESET menu.