A M P 1 I N T E G R AT E D P O W E R A N D E N E R G Y I N S TA L L AT I O N I N S T R U C T I O N S
AMP1
BACnet programming information (cont.)
BACnet protocol implementation conformance
statement (PICS)
Date: January 1, 2013
Vendor Name: GE Industrial Solutions
Product Name: AMP1H5 Energy Meter
Product Model Number: AMP1H5
Applications Software Version: 1
Firmware Revision: x.xxx
BACnet Protocol Revision: 4
Product Description: 3-phase electrical energy meter
BACnet standardized device profile (Annex L): BACnet
Application Specific Controller (B-ASC)
List all BACnet interoperability building blocks supported
(Annex K): DS-RP-B, DS-RPM-B, DS-WP-B, DM-DDB-B,
DM-DOB-B, DM-DCC-B, T-VMT-I-B, DM-TS-B
Segmentation capability: Segmentation not supported
Standard object types supported: No dynamic Creation or
Deletion supported; no proprietary properties or object types
1. Device object
Optional Properties Supported
• Max_Master, Max_Info_Frames, Description, Location,
Local_Time, Local_Date
Writable Properties
• Object_Identifier, Object_Name, Max_Master, Location
Property Range Restrictions
• Object_Identifier – May only write values from 1 to 4,193,999
• Location (limited to 64 characters); Max_Master – May only
write values from 1 to 127
2. Analog_input objects
Optional Properties Supported
• Description, Reliability
• No Writable Properties
3. Analog_value objects
Optional Properties Supported
• Description, Reliability
• Writable Properties : Only the Present_Value is writable
• Property Range Restrictions
- AV1: May only write 30078, 21211, 21212 and 16498
- AV2: May only write 10, 11, 12, 31 and 40
- AV3: May only write values from 5 to 32000
- AV4: May only write values 1 and 3
- AV5: May only write values from 0.01 to 320.0
For troubleshooting or service related questions, contact ABB at 800-782-8061 or at epis.component.support@abb.com
- AV6: May only write values such that AV6/AV5 is from 82 to
660 (absolute range is 82-32000). To ensure AV6 accepts/
rejects the proper values, set AV5 first.
- AV7: May only write values 0 and 1
- AV8: May only write values from 1 to 99
- AV9: May only write values from 1 to 99
- AV10: May only write values from 1 to 6
- AV11: May only write the value 0 or a value from 1000 to
3276700 in multiples of 100. The Record_Count of the
Trend_Logs (TL1 to TL3) are reset when this object is
written.
4. Binary_input objects
Optional Properties Supported
• Description, Reliability
• No Writable Properties
5. Trend_log objects
Optional Properties Supported
• Description
• Writable Properties
- Log_Enable, Start_Time, Stop_Time, Log_DeviceObject-
Property, Log_Interval, Stop_When_Full, Record_Count
• Property Range Restrictions
- Log_DeviceObjectProperty: May only be set to the
Present_Value of local objects AI1 through AI44 (only the
Present_Value of objects AI1 through AI44 may be logged)
- Log_Interval: May only write the value 0 or values from
1000 to 3276700 in multiples of 100
Data link layer options: BMS/TP master (Clause 9), baud
rate(s): 9600, 19200, 38400, 76800, 115200
Device address binding: Static device binding is not
supported
(No client functionality is included)
Networking options: None
Character sets supported: ANSI X3.4
Legend
The following table lists the addresses assigned.
R=read only; R/W=read from either int or ¯oat formats,
R/W
write only to integer format.
Value is stored in non-volatile memory. The value will still be
NV
available if the meter experiences a power loss and reset.
Units
Lists the physical units that a register holds.