A M P 1 I N T E G R AT E D P O W E R A N D E N E R G Y I N S TA L L AT I O N I N S T R U C T I O N S
22
AMP1
Analog_input objects (cont.)
No.
Name
Description
KW_Max_
Total Real Power
AI37
Demand
Maximum Demand
KVAR_Max_
Total Reactive Power
AI38
Demand
Maximum Demand
KVA_Max_
Total Apparent Power
AI39
Demand
Maximum Demand
AI40
Pulse_Count_1
Pulse Count #1
AI41
Pulse_Count_2
Pulse Count #2
Real Energy
AI42
KWH_A
Consumption
Phase A
Real Energy
AI43
KWH_B
Consumption
Phase B
Real Energy
AI44
KWH_C
Consumption
Phase C
Theoretical Maximum
AI45
Max_Power
System Power
AI46
Reserved_AI46
Reserved
Count of Energy
AI47
Energy Resets
Accumulator Resets
AI48
Reserved_AI48
Reserved
AI49
Reserved_AI49
Reserved
AI50
Power Up Count Power Up Counter
AI51
Ouput Config
Ouput Configuration
AI52
Reserved_AI52
Alert Summary Register
For troubleshooting or service related questions, contact ABB at 800-782-8061 or at epis.component.support@abb.com
R/W NV
Units
Range
0 - Max_Power
R
NV
kW
(AI45)
0 - Max_Power
R
NV
kVAR
(AI45)
0 - Max_Power
R
NV
kVA
(AI45)
R
NV
#
0 - 4294967040
R
NV
#
0 - 4294967040
R
NV
kWh
0 - 3.4+E38
R
NV
kWh
0 - 3.4+E38
R
NV
kWh
0 - 3.4+E38
R
NV
kW
0 - 1.84467e19
R
0
R
NV
0 - 32767
R
0
R
0
R
NV
0 - 32767
R
NV
0 - 15
R
0 - 32767
Additional information
This retains the largest value measured for Total
Real Power Demand (AI34) for any single demand
interval since the Max Demand were last explicitly
reset via AV1 (this is also reset when the demand
interval is changed).
This retains the largest value measured for Total
Reactive Power Demand (AI35) for any single
demand interval since the Max Demand were last
explicitly reset via AV1 (this is also reset when the
demand interval is changed).
This retains the largest value measured for Total
Apparent Power Demand (AI36) for any single
demand interval since the Max Demand were last
explicitly reset via AV1 (this is also reset when the
demand interval is changed).
Running count of contact closures on Pulse1 input
since last reset. Write 16498 (0x4072) to the
Present_Value property of Analog_Value object AV1
to reset both Pulse Counters to 0.
Pulse Count 2; Running count of contact closures on
Pulse2 input since last reset. Write 16498 (0x4072)
to the Present_Value property of Analog_Value
object AV1 to reset both Pulse Counters to 0.
Theoretical Maximum System Power – This is the
theoretical maximum power the meter expects to
see on a service. It is calculated by the meter from
the System Type (in object AV2), CT Size (in object
AV3), and System Voltage (in object AV6) - Power
Factor is assumed to be unity. The register is
updated whenever the user changes any of these
parameters.
Returns QNAN or any value
Running count of how many times the energy
counter
has been reset
Returns QNAN or any value
Returns QNAN or any value
Running count of product power-up cycles (Control
Power)
Returns "0"
This contains a decimal value that represents the
status of all Binary_Object alert values in one
number that can be read without having to access
mulitple objects. It is a decimal representation of a
15-bit hexidecimal value produced by combining the
15 alert bits into one number, where the bit value of
Object BI1 is the least significant bit and BI15 is the
most significant bit.