A M P 1 I N T E G R AT E D P O W E R A N D E N E R G Y I N S TA L L AT I O N I N S T R U C T I O N S
AMP1

Analog_input objects

Use the Present_Value property of the Analog_Input objects
for all read-only numeric variables in the meter other than
those used specifically for device configuration (in the Device
Object) or data logging (in the Trend_Log objects).
These objects support the Description and Reliability object
properties and all required Analog_Input object properties.
None of them are writable. The values that are not
instantaneous (i.e., Accumulated Energy, Max Demand, Pulse
Input Counts) are non-volatile. They are not updated while
No.
Name
Description
AV1
Energy
Real Energy Consumption
AV2
kW_Total
Total Real Power
AV3
kVAR_Total
Total Reactive Power
AV4
kVA_Total
Total Apparent Power
AV5
PF_Total
Total Power Factor
AV6
Volts_LL_Avg
Voltage L-L Average
AV7
Volts_LN_Avg
Voltage L-N Average
AV8
Current_Avg
Current Average
AV9
kW_A
Real Power Phase A
AV10
kW_B
Real Power Phase B
AV11
kW_C
Real Power Phase C
AI12
PF_A
Power Factor Phase A
AI13
PF_B
Power Factor Phase B
AI14
PF_C
Power Factor Phase C
AI15
Volts_AB
Votlage Phase A-B
AI16
Volts_BC
Voltage Phase B-C
AI17
Volts_AC
Voltage Phase A-C
AI18
Volts_AN
Voltage Phase A-N
AI19
Volts_BN
Voltage Phase B-N
AI20
Volts_CN
Voltage Phase C-N
AI21
Current_A
Current Phase A
AI22
Current_B
Current Phase B
AI23
Current_C
Current Phase C
AI24
Reserved_AI24
Reserved
AI25
Frequency
Frequency
Apparent Energy
AI26
kVAh
Consumption
Reactive Energy
AI27
kVARh
Consumption
AI28
kVA_A
Apparent Power Phase A
AI29
kVA_B
Apparent Power Phase B
AI30
kVA_C
Apparent Power Phase C
AI31
KVAR_A
Reactive Power Phase A
AI32
KVAR_B
Reactive Power Phase B
AI33
KVAR_C
Reactive Power Phase C
KW_Present_
Total Real Power Present
AI34
Demand
Demand
KVAR_Present_
Total Reactive Power
AI35
Demand
Present Demand
KVA_Present_
Total Apparent Power
AI36
Demand
Present Demand
For troubleshooting or service related questions, contact ABB at 800-782-8061 or at epis.component.support@abb.com
control power is inactive, but their past values are retained
when power is restored.
For complete assurance, check the Reliabilty property for a
No_ Fault_Detected status before reading the Present_Value.
If the line voltage or input frequency of the system being
monitored falls out of the supported range, the corresponding
alert bits (BI1-BI7) are set and the reliability property of any
values that cannot be accurately measured under those
conditions returns Unreliable_Other.
R/W NV
Units
Range
R
NV
kWh
0 - 3.4+E38
R
kW
0 - Max_Power (AI45)
R
kVAR
0 - Max_Power (AI45)
R
kVA
0 - Max_Power (AI45)
R
Power Factor 0.00 - 1.00
R
Volts
R
Volts
R
Amps
R
kW
0 - Max_Power (AI45)
R
kW
0 - Max_Power (AI45)
R
kW
0 - Max_Power (AI45)
R
Power Factor 0.00 - 1.00
R
Power Factor 0.00 - 1.00
R
Power Factor 0.00 - 1.00
R
Volts
R
Volts
R
Volts
R
Volts
R
Volts
R
Volts
R
Amps
R
Amps
R
Amps
R
n/a
R
Hz
45.0-65.0
R
NV
kVAh
0 - 3.4+E38
R
NV
kVARh
0 - 3.4+E38
R
kVA
0 - Max_Power (AI45)
R
kVA
0 - Max_Power (AI45)
R
kVA
0 - Max_Power (AI45)
R
kVAR
0 - Max_Power (AI45)
R
kVAR
0 - Max_Power (AI45)
R
kVAR
0 - Max_Power (AI45)
R
kW
0 - Max_Power (AI45)
R
kVAR
0 - Max_Power (AI45)
R
kVA
0 - Max_Power (AI45)
Additional information
1.00 for 100%
1.00 for 100%
1.00 for 100%
1.00 for 100%
Returns QNAN or any value
Returns QNAN if frequency is out of range (or no voltage
input present on Phase A)
The UNITS property of object AI26 reports that these
units are kWh because there is no unit type in the
BACnet standard for kVAh.
The UNITS property of object AI27 reports that these
units are kWh because there is no unit type in the
BACnet standard for kVARh.
table continued on next page
21