A M P 1 I N T E G R AT E D P O W E R A N D E N E R G Y I N S TA L L AT I O N I N S T R U C T I O N S
AMP1

User interface for setup

To: SPASS
Back
S BAC
SETUP > PASWD
Back
S CT
Transformer
Back
S SYS
System
Type
S PT
Back
Potential
Transformer
Back
S
V
System
Voltage
Back
S PWR
System
Voltage
To Setup p. 2 "SPLOS"
For troubleshooting or service related questions, contact ABB at 800-782-8061 or at epis.component.support@abb.com
KBAUD
--------
MAC
115.2
ID1
--------
76.8
--------
001
38.4
0000
19.2
9.6
CT V
CT SZ
--------
--------
1.0
200
.33
Next
SYSTM
--------
3L-1n
3L
2L-1n
2L
1L+1n
Next
RATIO
--------
001.00
Next
V LL
--------
00480
Next
MX KW
--------
103.92
Next
Note: Bold is the default.
Note: Bold is the Default.
Set communications parameters:
ADDR – BACnet MS/TP MAC Address: 0 – 127.
+ increments the selected (blinking) digit.
– selects the digit to the left.
BAUD - Baud Rate: 9600 – 115200 Baud
BACnet ID: These two screens set the 7 digit
BACnet device ID. Screen ID1 is the most
signi¦cant 4 digits and ID2 the least signi¦cant
three digits. This is in the range of 0 - 4,194,302.
ID2
--------
000
Set Current Transducer:
CT V - CT Input Voltage: + or – to Select 1.0 or .33V.
Next
CT SZ - CT Size: in Amps. Maximum is 32000 Amps.
Set system configuration:
SYSTM: + or – to step through the following System
Type options:
System Reg 130 CTs
3L-1n
40
3L
31
2L-1n
12
2L
11
1L-1n
10
Set potential transfomer ratio:
RATIO – Potential transformer step down is
RATIO:1. Default is 1:1 (No PT installed). See Install
for wiring diagrams. This value must be set before
the System Voltage (if used).
Set system voltage:
V LL – The nominal Line to Line Voltage for the
system. This is used by the meter to calculate the
theoretical maximum system power, and as the
reference voltage for setting the Phase Loss
threshold. Maximum is 32000 Volts. For system
type 1+N (10), this is a Line to Neutral Voltage,
indicated by "V LN". Note: the meter will reject
settings that are not within the meter's operating
range when divided by the PT ratio.
System power:
MX KW – The theoretical Maximum System Power is
calculated by the meter from the System Voltage,
CT size, and System Type. Power Factor is assumed
to be unity. The value of System Power is used to
determine which combinations of pulse weight and
duration are valid and will keep up with the
maximum power the meter will see. This value
is read only.
Description
3
Wye Three Phase: A, B, &
C with Neutral (Default).
3
Delta Three Phase: A, B &
C; no Neutral
2 S
Single Split Phase: A & B
with Neutral
1
Single Phase: A & B; no
Neutral
1
Single Phase: A to
Neutral
13