A M P 1 I N T E G R AT E D P O W E R A N D E N E R G Y I N S TA L L AT I O N I N S T R U C T I O N S
AMP1
Device object
Property
Object_Identifier
Object_Type
Object_Name
Vendor_Name
Vendor_Identifier
Model_Name
Firmware_Revision
Application_Software_
Version
Location
Description
Protocol_Version
Protocol_Revsion
Local_Date
Local_Time
Segmentation_Supported
Max_Master
Max_Info_Frames
Max_APDU_Length_Accepted
APDU_Timeout
Number_of_APDU_Retries
System_Status
Protocol_Sevices_Supported
011110000
Protocol_Object_Types_
Supported
Object_List
Device_Address_Binding
Database_Revsion
For troubleshooting or service related questions, contact ABB at 800-782-8061 or at epis.component.support@abb.com
R/W
NV
Value Returned
R/W
NV
Device<n>
R
NV
Device (8)
GE AMP1xx Series Energy Meter - S/N: <serial
R
NV
number>
R
NV
GE Industrial Solutions
R
NV
276
R
NV
AMP1H5 Energy Meter
R
NV
<Current Revision #>
R
NV
<Current version #>
R/W
NV
<Location>
R
NV
GE AMP1H5 Energy Meter S/N: <serial number>
R
NV
1
R
NV
4
R
Date
R
Time
R
NV
NO_SEGMENTATION (3)
R/W
NV
1-127 (Factory Default is 127)
R
NV
1
R
NV
480
R
NV
60000
R
NV
0
R
NV
Operational (0)
R
NV
0b0000000000001011010000000000000
R
NV
R
NV
0b1011000010000000000010000000000
DE1,AI1,AI2,AI3,AI4,AI5,AI6,AI7,AI8,AI9,AI10,AI11
,AI12, AI13,AI14,AI15,AI16,AI17,AI18,AI19,AI20,AI21
,AI22,AI23, AI24,AI25,AI26,AI27,AI28,AI29,AI30,AI3
1,AI32,AI33,AI34,AI35,AI36,AI37,AI38,AI39,AI40,AI4
R
NV
1,AI42 ,AI43,AI44,AI45,AI46,AI47,AI48,AI49,AI50,AI
51,AI52,AV1,AV2,AV3,AV4,AV5,AV6,AV 7,AV8,AV9,A
V10,AV11,BI1,BI2,BI3,BI4,BI5, BI6,BI7,BI8,BI9,BI10,B
I11,BI12,BI13,BI14,BI15,TL1,TL2,TL3
R
NV
{}
R
0
Additional information
n is the 7 digit ID # set in the ID1 & ID2 setup
screens on the meter. The BACnet Device ID is a
decimal number from 1 to 4,193,999 that can be
entered or viewed on the user screens or
through this property. The default value set at
the factory is a psuedo-random number from
1,000,000 to 3,097,151 to reduce the likelihood
of con¯icts if multiple units are installed using
their default IDs.
"xyyy". This is the BACnet processor firmware
version in the format <xyyy>, with an implied
decimal point between the first two digits (x.
yyy)
"RS= xyyy, OS=xyyy, BACnet Gateway=xyyy". The
format <xyyy> has an implied decimal point
between the first two digits (x.yyy).
Limted to 64 Characters – Default value is
"Installed location not yet identified".
BACnet Protocol Version 1
BACnet Protocol Revision 4
Set via BACnet Time Synchronization only –
reverts to Jan 1, 2000 if control power drops.
Set via BACnet Time Synchronization only –
reverts to 12:00:00 AM if control power drops.
Segmentation is not supported.
Highest possible MAC Address for Master nodes
on the local MS/TP network.
Maximum number of information frames
allowed before passing the MS/TP token.
19