Product Identification - ABB GE ReliaGear AMP1 Installation Instructions Manual

Table of Contents

Advertisement

6
AMP1

Product identification

Description
AMP1H5
BACnet MS/TP protocol output;
Modbus full data set, data logging;
pulse input (2 pulses)
Dimensions
2.3"
(59mm)
2.3"
(59mm)
4.2"
(107mm)
4.2"
(107mm)
DIN mount configuration
Bottom view
1.9"
3.6"
(91 mm)
3.6"
(91 mm)
0.2"
(4 mm)
0.2"
(4 mm)
Screw mount configuration
Bottom view
+
3.9"
(99 mm)
4.3"
(109 mm)
For troubleshooting or service related questions, contact ABB at 800-782-8061 or at epis.component.support@abb.com
A M P 1 I N T E G R AT E D P O W E R A N D E N E R G Y I N S TA L L AT I O N I N S T R U C T I O N S
1.8"
(45mm)
1.8"
(45mm)
1.9"
(48mm)
1.9"
(48mm)
1.5
(39mm)
1.5
(39mm)
3.6"
(91mm)
3.6"
(91mm)
4.2"
(107 mm)
4.2"
(107 mm)
2.4"
(61 mm)
1.2"
(31 mm)
0.3"
+
(8 mm)
0.4"
+
(10 mm)
Product overview
The AMP1H5 DIN Rail Power Meter provides a solution for
measuring energy data with a single device. Inputs include
Control Power, CT, and 3-phase voltage. The meter supports
BACnet MS/TP protocol and has data logging capability and
two pulse contact inputs. The LCD screen on the faceplate
allows instant output viewing.
The meter is housed in a plastic enclosure suitable for
installation on T35 DIN rail according to EN50022. It can be
mounted with any orientation over the entire ambient
temperature range, either on a DIN rail or in a panel. The
AMP1H5 meter is not sensitive to CT orientation to reduce
installation errors.
Data output
Full Data Set (FDS)
• Power (kW)
• Energy (kWh)
• Configurable for CT & PT ratios, system type, and passwords
• Diagnostic alerts
• Current: 3-phase average
• Volts: 3-phase average
• Current: by phase
2.4"
(61 mm)
2.4"
• Volts: by phase Line-Line and Line-Neutral
(61 mm)
1.2"
• Power: Real, Reactive, and Apparent 3-phase total and per
(31 mm)
1.2"
+
(31 mm)
phase
+
• Power factor: 3-phase average and per phase
• Frequency
3.9"
• Power demand: most Recent and Peak
(99 mm)
3.9"
• Demand configuration: Fixed, Rolling Block, and External
(99 mm)
4.3"
Sync (Modbus only)
(109 mm)
4.3"
(109 mm)
• Real Time Clock: uses BACnet Time Synchronization services
+
Data logging (includes all FDS outputs, plus)
+
• 3 BACnet Log_Events: each buffer holds 5760 time-stamped
• 32-bit entries (user configures which 3 data points are
stored in these buffers)
• User configurable logging interval (when configured for a 15
minute interval, each buffer holds 60 days of data)
• • Continuous and Single Shot logging modes: user selectable
0.3"
+
(8 mm)
0.3"
+
(8 mm)
0.4"
(10 mm)
0.4"
(10 mm)