Terminal
Number
22
Digital Input 3
(Reset)
23
Digital Input 2
(Stop)
24
Digital Input 1
(Start)
25
24 VDC Isolated Common
26
Snubber Resistor Braking
Control Signal
27
+24 VDC Isolated Common
7 14
Downloaded from StockCheck.com
Table 7.1 Wiring Signal and Control I/O to the Terminal Strip (Continued)
Description
Wiring the Reset Input
Wiring the Stop/Start Inputs
Wiring the Snubber Resistor
Parameters/Wiring Connections
The following parameter must be set:
P .000: Control Source
Terminal 22 On = Reset
The following parameter must be set:
P .000: Control Source
P .025: Stop Type
Terminal 23 Off = Stop
Terminal 24 On Transition = Start
Used with Snubber Resistor Braking Kit M/N 2DB4010.
Refer to the kit's instruction manual for installation
instructions.