0 10 VDC or 4 20 mA
Analog Output Reference
11
Regulator Common
7 8
Downloaded from StockCheck.com
Table 7.1 Wiring Signal and Control I/O to the Terminal Strip (Continued)
Wiring Analog Outputs
The setting of parameter P .012 selects the terminal strip
analog output source (either speed or torque). Jumper J17
must also be set. See figure 2.11. The 4 20mA current
selection requires a power supply for operation. The power
can be sourced from the pulse tachometer supply, terminal
4 (15VDC), or from an external 15V power supply. Note that
the maximum supply current from terminal 4 is 250mA
(pulse tachometer and current source) at 15V. Terminals 9
and 11 are internally connected.
Load
(Meter or Analog Input)
+
Connection to the negative side of the
power supply is only required
when an external 15V power supply is used.